459669
47
Zoom out
Zoom in
Previous page
1/60
Next page
47 / 60
Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en
Building Technologies Functions 19 Jun 2009
4.15.2 Parameters of the "Expert level
with diagnostics and test"
Parameter
Name Factory setting Range
RDG100
RDG100T
RDG110
RDG140
RDG160
Ex
p
ert level
P30 P-band / switching differential in heating mode 2 K 0.5…6 K

P31 P-band / switching differential in cooling mode 1 K 0.5…6 K

P32 P-band / switching differential for radiator 2 K 0.5…6 K

P33 Dead zone in Comfort mode 2 K 0.5…5 K

P34 Setpoint differential (w
D
) 2 K 0.5…5 K

P35 Integral action time 5 min 0…10 min


P36 Heating / cooling changeover cooling (X1/X2) 16 °C 10…25 °C

P37 Heating / cooling changeover heating (X1/X2) 28 °C 27…40 °C

P38 Functionality of X1 1 = external sensor 0 = --- (no function)
1 = room temp ext / ret air temp (AI)
2 = H/C changeover (AI/DI)
3 = operating mode contact [DI)
4 = dewpoint sensor (DI)
5 = enable electrical heater (DI)
6 = fault input (DI)
0..6
0..6
0..6
0..6
0..6
P39 Operating action of X1 if digital input 0 (NO) 0 = normally open / open
1 = normally closed / closed

P40 Functionality of X2 2 = H/C changeover 0 = --- (no function)
1 = room temp ext / ret air temp (AI)
2 = H/C changeover (AI/DI)
3 = operating mode contact [DI)
4 = dewpoint sensor. (DI)
5 = enable electrical heater (DI)
6 = fault input (DI)
0..6
0..6
0..6
0..6
0..6
P41 Operating action of X2 if digital input 0 (NO) 0 = normally open / open
1 = normally closed / closed

P42 Functionality of D1 3 = operating mode
changeover
0 = --- (no function)
2 = H/C changeover (DI)
3 = operating mode contact [DI)
4 = dewpoint sensor (DI)
5 = enable electrical heater (DI)
6 = fault input (DI)
0..6
0..6
0..6
0..6
0..6
P43 Operating action of D1 if digital input 0 (NO) 0 = normally open / open
1 = normally closed / closed

P44 Running time of Y1/Y2 output
(only with modulating PI control)
150 s 20…300 s


P45 Running time of Y3/Y4 output
(only with modulating PI control)
150 s 20…300 s


P46 Output Y1/Y2 (if not parameterized as 3-pos.) ON/OFF (1) 1 = 2-position
2 = PWM


P47 Output Y3/Y4 (if not parameterized as 3-pos.) ON/OFF (1) 1 = 2-position
2 = PWM


P48 Min. output on time
2-position control output
1 min. 1...20 min.


P49 Min. output off time
2-position control output
1 min. 1...20 min.


P50 Purging function (only when changeover with local
sensor is selected)
OFF OFF: Not active
1…5 min: Active with selected duration

P51 Floor heating limit temperature OFF OFF, 10...50 °C

Parameter available
Parameter not available
P46, P47: Setting to 2-position or 3-position is made with DIP switches 4 and 5.
Note
47


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDG140 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDG140 in the language / languages: English as an attachment in your email.

The manual is 3,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDG140

Siemens RDG140 User Manual - German - 64 pages

Siemens RDG140 User Manual - French - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info