459669
49
Zoom out
Zoom in
Previous page
1/60
Next page
49 / 60
Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en
Building Technologies Handling 19 Jun 2009
5 Handling
5.1 Mounting and installation
Do not mount on a wall in niches or book-
shelves, behind curtains, above or near
heat sources, or exposed to direct solar
radiation. Mount about 1.5 m above the
floor.
The room thermostat must be mounted in a clean, dry indoor place and must not be
exposed to drip or splash water
See Mounting Instructions (M3181) enclosed with the thermostat.
Comply with local regulations to wire, fuse and earth the thermostat
Size correctly the cables to the thermostat, fan and valve actuators for AC 230 V
mains voltage
Use only valve actuators rated for AC 230 V on RDG100… / RDG110
The power supply line must have an external fuse or circuit breaker with a rated
current of no more than 10 A
Isolate the cables of inputs X1-M / X2-M and D1-GND if the conduit box carries
AC 230 V mains voltage
On the RDG100.. and RDG110, inputs X1-M and X2-M carry mains potential.
If the sensor’s cables are extended, they must be suited for mains voltage
Inputs X1-M, X2-M or D1-GND of different units (e.g. summer / winter switch)
may be connected in parallel with an external switch. Consider overall maximum
contact sensing current for switch rating
Disconnect power supply before removing the thermostat from the mounting
plate!
Select the application and the type of control output via the DIP switches before
fitting the thermostat to the mounting plate.
After power is applied, the thermostat carries out a reset during which all LCD
segments blink, indicating that the reset was correct. After the reset, which takes
about 3 seconds, the thermostat is ready for commissioning by qualified HVAC
staff.
The control parameters of the thermostat can be set to ensure optimum
performance of the entire system (see section 4.15, control parameters).
The control sequence may need to be set via parameter P01 depending on the
application. The factory setting for the 2-pipe application is “Cooling only”; and
“Heating and cooling” for the 4-pipe application
When the thermostat is used in connection with a compressor, the minimum
output on-time (parameter P48) and off-time (parameter P49) for Y11/Y21 must
be adjusted to avoid damage to the compressor and shortening its life
Recalibrate the temperature sensor if the room temperature displayed on the
thermostat does not match the room temperature measured. To do this, change
parameter P05
We recommend to review the setpoints and setpoint setting ranges (parameters
P08…P12) and change them as needed to achieve maximum comfort and save
energy
Mounting
Wiring
Commissioning
Control sequence
Compressor-based
application
Calibrate sensor
Setpoint and setpoint
setting range limitation
49


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDG140 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDG140 in the language / languages: English as an attachment in your email.

The manual is 3,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDG140

Siemens RDG140 User Manual - German - 64 pages

Siemens RDG140 User Manual - French - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info