INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT
-
35
-
The parameter setting is ranging from 0 – 100%; the default value is 20%.
The instructions for changing this parameter can be found in chapter 4.
The Room differential parameter determines when the weather-compensated heating is put out of
operation according to the moment when the required temperature in the reference room HC1 is
exceeded.
The parameter setting is ranging from 0 – 5°C; the default value is 1°C.
The instructions for changing this parameter can be found in chapter 4.
The Hysteresis parameter is related to the Room differential parameter. It determines when the
weather-compensated heating is put back into operation according to the required temperature in
the reference room HC1.
The parameter setting is ranging from 0 – 5°C; the default value is 0.5°C.
The instructions for changing this parameter can be found in chapter 4.
Example: - The Comfort HC1 parameter is 22°C
- The Room differential parameter is 1°C
- The Hysteresis parameter is 0.8°C
The heating turns off if the temperature in the reference room is 23°C (22+1=23).
The heating turns on again if the temperature in the reference room falls to 22.2°C (22+1-
0.8=22.2).
T
SKUT
- Real temperature in the reference room
DIF - Room differential
HYS - Hysteresis
Q2 - Pump HC1
The function Quick setback offers selections OFF and ON.
The selection OFF causes an increase in the heating curve according to the set parameters of the
required room temperatures during the transition to the mode “reduce”. However, the room is still
tempered. (It concerns the operation of the weather-compensated circuit without the installed
room temperature sensor.)
The selection ON causes that during the transition to the mode “reduce” the pump Q2 of the
heating circuit 1 turns off (if it is a mixing circuit) and the mixing valve Y1 is closed.
a) Function with the room temperature sensor – heating is off till the room temperature falls to
the required temperature of the mode “reduce”. Then the pump Q2 of the heating circuit 1 is
activated and the mixing valve is opened – see picture below.
b) Function without the room temperature sensor
the quick setback turns off heating for a
certain period of time that depends on the outside temperature and the time constant of the
35


Need help? Post your question in this forum.

Forumrules
1

Forum

siemens-climatix-2

Reset search

  • salve
    chiedo se è possibile fare un by pass per far partire il sistema di condizionamento a causa dell'oscuramento :del controllore POL/STD
    grazie
    Submitted on 11-3-2022 at 12:44

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens Climatix 2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens Climatix 2 in the language / languages: English as an attachment in your email.

The manual is 1,35 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info