CM2N3204E / 1.1999 Siemens Building Technologies
4/20 Landis & Staefa Division
This function is intended to make optimum use of the cooling energy supplied to the
plant. Based on the measured differential of outside and room or extract air tempera-
ture, the plant is operated either with reduced amounts of outside air or with heat recov-
ery.
In that case, the controller overrides normal control and acts on position signal output
Y30 to position it to 100 % with HR (DC 10 V) or to Y30
min.
. This function can be se-
lected (DIL switch no. 3).
10
0
T
B4 < B1
B4 > B1
B4 > B1
10
0
10
0
Y30 [V]
min
Y30
min
Y30
00
B4 < B1
T
10
0
2 K2 K
Y30 [V] Y30 [V] Y30 [V]
T
T
3204D02E
Mixing dampers HR equipment
During non-occupancy periods, «Unoccupied heating mode» or «Unoccupied cooling
mode» is automatically used, provided enabling took place (can be set for each func-
tion) and the respective preconditions are met. The factory-set minimum operating time
is 30 min (adjustable from 0 to 12 h).
«Unoccupied heating mode» becomes active when the set supporting level for heat-
ing (adjustable from 0 to 30 °C) is reached. Heating is provided until the room or extract
air temperature exceeds the supporting level by 1 K. In that case, the fans run at speed
I or II (depending on the preselected speed). Outputs Y20 and Y30 with operating action
« \ » are disabled (0 %).
«Unoccupied cooling mode» becomes active when the set supporting level for cooling
(adjustable from 20 to 50 °C) is reached. Cooling is provided until the room or extract air
temperature falls below the supporting level by 1 K. In that case, the fans run at speed I
or II (depending on the preselected speed). Outputs Y10 and Y30 with operating action
« \ » are disabled (0 %).
During non-occupancy periods in the summer, this function is automatically activated if
- the function has been enabled
- both the room and the outside temperature exceed their adjusted limits, and
- the difference between room and outside temperature exceeds the value set.
If the function is activated, cool outside air is drawn into the building. In that case, the
fans run at speed I or II (depending on the preselected speed). Outputs Y10, Y20 and
Y30 with operating action « \ » are disabled (0 %). The factory-set minimum operating
time is 30 min. It is adjustable (from 0 min to 12 h).
Maximum Economy
Changeover (MECH)
Unoccupied heating
and cooling mode
Night purging
4


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens AEROGYR RWI65.02 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens AEROGYR RWI65.02 in the language / languages: English as an attachment in your email.

The manual is 0,25 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens AEROGYR RWI65.02

Siemens AEROGYR RWI65.02 User Manual - German - 50 pages

Siemens AEROGYR RWI65.02 Usermanual and installation guide - Dutch - 73 pages

Siemens AEROGYR RWI65.02 User Manual - French - 22 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info