Siemens Building Technologies CM2N3204E / 1.1999
Landis & Staefa Division 3/20
Room-supply air temperature or extract air-supply air temperature cascade control.
The connection of room or extract air temperature detectors (terminal B1) and supply
air temperature detectors (terminal B2) automatically activates cascade control.
With cascade control, the room or extract air temperature is maintained at a constant
level. The room or extract air temperature is the controlled variable whose setpoint
can be read off and adjusted on the controller’s second operating level.
The supply air temperature is shifted in function of the deviation of the room / extract
air temperature from the setpoint of room / extract air temperature. The extent of set-
point shift is calculated via the cascade authority (adjustable from 0 to 20).
- Room-supply air temperature or extract air-supply air temperature cascade control
with fixed supply air limitations (mode of control 1).
If the supply air temperature falls below the limit set on the controller, the inbuilt
minimum limitation will take command of control to prevent the supply air tempera-
ture from falling further.
The set limit is maintained at a constant level. The same considerations apply to
maximum limitation.
- Room-supply air temperature or extract air-supply air temperature cascade control
with shifting supply air limitations (displacement ventilation) (mode of control 2).
The shifting limits of the supply air temperature are calculated in function of the ac-
tual room or extract air temperature, whereby the supply air temperature must re-
main within the boundaries dictated by the selected values of minimum and maxi-
mum limitation.
Supply air temperature control (mode of control 3).
If a supply air temperature detector (terminal B2) is connected, supply air temperature
control is automatically activated. With this mode of control, the supply air temperature
is maintained at a constant level.
The required mode of control can be selected.
The RWI65.02 is a sequence controller with three modulating outputs (Y10 = heating,
Y20 = cooling, Y30 = HR) and one switching output (Q13/Q24 = cooling).
It allows control sequences using both operating actions, for dampers and HR equip-
ment. Both operating action and control sequences are adjustable (DIL switches no. 4
to 7).
100
Y30
min
Y10/Y30 Y30/Y10
Y20
SA
SD
T
w
h
w
c
X
P1
T
n1
X
P3
T
n3
X
P2
T
n2
Y [ % ]
3204D03E
(DtPnt 33)
(DtPnt 32)
(DtPnt 6)
The basis used for compensation are the setpoints selected on the controller. These
basic setpoints can be shifted as follows:
compensation of controller setpoint in function of the outside temperature (terminal
B4); with this function, summer/winter compensation is integrated in the controller; the
compensation characteristic is adjustable
compensation by means of an active or passive setting unit, either as an absolute
setpoint or in the form of setpoint shifting via signal input «Z»
compensation across the entire setpoint range by a Landis & Staefa building auto-
mation system via the FLN bus and FLN communication insert AZI65.1
Temperature control
Control sequences
and operating action
Function diagram
Setpoint compensation
3


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens AEROGYR RWI65.02 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens AEROGYR RWI65.02 in the language / languages: English as an attachment in your email.

The manual is 0,25 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens AEROGYR RWI65.02

Siemens AEROGYR RWI65.02 User Manual - German - 50 pages

Siemens AEROGYR RWI65.02 Usermanual and installation guide - Dutch - 73 pages

Siemens AEROGYR RWI65.02 User Manual - French - 22 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info