16 SATEL Installer Manual
The spring on the tamper contact must cling to the mounting surface so that the contact
opens at any attempt to pull off the keypad from the wall. The keypad tamper contact has no
connection with the system tamper circuit. Its state is defined by the control panel, based on
the data received from the keypad. In case two keypads are connected in parallel, the control
panel will detect tampering when both contacts are open. When the control panel is in the
service mode, the tamper contact and the keypad address are not controlled. Should the
panel alarm at the moment of exiting the service mode, it would mean an incorrectly
programmed address, or opening of the tamper contact.
Connection of detectors
The CA-6 can operate with detectors of any type. Each zone of the control panel can work in
the configuration NC, NO, EOL, 2EOL/NO, 2EOL/NC. When the zone works in an EOL
configuration, a 2.2 k resistor should be used to make the detector circuit. In case of 2EOL
configuration, the detector circuit is closed by two 1.1 k resistors. This type of zones
enables the status of detector and its tamper contact to be monitored at the same time.
The detectors may be supplied from any of the electronically protected outputs (OUT1 to
OUT3). The output should be programmed as the "POWER SUPPLY OUTPUT" (function
number 27). The use of OUT3 is suggested.
Separation of the detector power supply ground and the line ground makes it possible to
eliminate the effect of wiring resistance. Assuming that the wire is rather short, and only one
detector is connected to it, the installation can be simplified by using one wire for the power
supply ground (GND) and the signaling ground. The NO and NC detectors in 2EOL
configuration are connected in the same way, it is only important to correctly indicate to the
control panel, what type of detector is connected to the zone input (2EOL/NO or 2EOL/NC).
The figures below only show how the alarm relay outputs should be connected. Proper
connection of the detectors will require that power supply (COM, 12 V) be provided and TMP
terminals (tamper contact) of EOL or NO/NC detectors be connected to the tamper circuit.
NC
NC TMP COM
12V
NC TMP
COM OUT3
DTA
CLK CTL COM
Z1
Z2
Z3 COM
Z4KPD
+
COM
CA-6
Fig. 6. Example of connecting NC type detector to control panel (NO type detector is to be
connected in the same way).
18


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Satel CA-6 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Satel CA-6 in the language / languages: English as an attachment in your email.

The manual is 0,56 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Satel CA-6

Satel CA-6 Additional guide - English - 40 pages

Satel CA-6 Quick start guide - English - 8 pages

Satel CA-6 Additional guide - German - 19 pages

Satel CA-6 User Manual - German - 19 pages

Satel CA-6 Installation Guide - German - 80 pages

Satel CA-6 User Manual - German - 18 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info