Problem display by blinker code
Installation instructions for qualified personnel
Important notes prior to
installation
Transport the unit in its original
packaging as close as possible
to the installation location.
You avoid transport damages
by doing so.
Check the contents of the
packaging for completeness
and check the unit for visible
transport damage. Report any
damage immediately to your
contractual partner and the
shipping company.
Lift the unit at the corners
and not by the refrigerant or
condensation connections.
The refrigerant pipes (injection
and suction line), valves and
connections must be insulated
against vapour diffusion.
If necessary, also insulate the
condensation pipe.
Select an installation location
which allows air to freely
flow through the inlet and
outlet. (See section "Minimum
clearances").
Do not install the unit in
the immediate vicinity of
devices with intensive thermal
radiation. Installation near
sources of thermal radiation
reduces the output of the unit.
Only open the shut-off valves
of the refrigerant lines after the
installation is complete.
Seal off open refrigerant lines
with suitable caps or adhesive
strips to avoid infiltration of
moisture and never kink or
compress the refrigerant lines.
Avoid unnecessary bends.
You thereby minimize loss of
pressure in the refrigerant lines
and ensure clear return flow of
the compressor oil.
Take special precautions with
regard to the oil return if the
exterior component is located
above the indoor unit.
See section "Oil return flow
measures".
If the basic length of the
refrigerant line exceeds 5
metres, add refrigerant.
The quantity of additional
refrigerant is provided in the
chapter "Add refrigerant".
Only use the union nuts for the
refrigerant pipes included in the
delivery, and remove them only
shortly before connecting the
refrigerant lines.
Make electrical connections in
accordance with the effective
DIN and VDE standards.
Always fasten electric cables
properly to the electrical
terminals. Otherwise a fire
could result.
Display Cause Required action
E0 EEPROM error Contact specialty company
E1
Communication error between outdoor component and
indoor unit
Disconnect from mains for 2 min, check wiring
E2 Wiring fault L/N/Pe/S Check wiring, replace IT circuit board
E3 Vaporiser fan speed too low Check wiring, check motor voltage
E5
Outdoor temp. sensor / condenser temperature fault /
short-circuited
Check wiring, contact specialty company
E6 air circulation sensor / vaporiser faulty / short-circuited Check wiring, contact specialty company
P0 IGBT electrical surge protection
Check wiring, check compressor wiring contact spe-
cialty company
P1 Electrical surge / Undervoltage protection
Check voltage on the L/N/S system. Switch off and
turn on again
P2
Excessive compressor temperature protection (Klixon) has
tripped
Check refrigerant quantity, wiring, Klixon
P4 IPM power board safety shutdown
Check wiring, switch off and on again, contact specialty
company
15
15


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO ML522 DC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO ML522 DC in the language / languages: English as an attachment in your email.

The manual is 1,92 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO ML522 DC

REMKO ML522 DC User Manual - German - 32 pages

REMKO ML522 DC User Manual - German - 32 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info