Edition GB - D04
REMKO BL
BL 261, BL 351
Wall - room air conditioner in split design
with quick-release coupling system
Operation · Technology · Spare parts
Contents
Carefully read this operating manual prior to commissioning / using
the equipment!
These instructions are an integral part of the unit and must always be
kept in the vicinity of the installation location or on the unit itself.
This operating manual is a translation of the German original.
Subject to modifications; no liability accepted for errors or misprints!
Safety notes 4
Environmental protection and recycling 4
Warranty 4
Intended use 4
Transportation and packaging 5
System description 5
Operation 6-12
Decommissioning 12
Care and maintenance 12-13
Troubleshooting and customer service 14-15
Installation instructions for qualified personnel 16-19
Installation 19
Connection of quick-release couplings 20
Leak testing 21
Pumping down to vacuum 21
Condensate draining and ensured discharge
21
Electrical connection 21-22
Electrical connection diagram 22
Electrical drawings 23
Before commissioning 24
Adding refrigerant 24
Commissioning 24-25
Unit dimensions 26
Exploded views 27-28
Spare parts lists 27-28
Technical data 29
EC – Declaration of Conformity 30
Made by REMKO
3
Safety notes
Disposing of the units and
their components
Only recyclable materials are used
in the manufacture of the units
and components.
Help protect the environment
by ensuring that the units or
components (for example
batteries) are not disposed of
in household waste, but only in
accordance with local regulations
and in an environmentally safe
manner, e.g. using authorised
disposal and recycling
specialists or council
collection points.
Intended use
Depending on the model, the
units and the additional fittings
with which they are equipped are
only intended for private use as
an air-conditioner for the purpose
of cooling or heating the air in an
enclosed space.
Any different or additional use shall
be classed as non-intended use.
The manufacturer/supplier assumes
no liability for damages arising from
such use. The user bears the sole
risk in such cases.
Intended use also includes
working in accordance with the
operating manual and installation
instructions and complying with the
maintenance requirements.
Carefully read this operating
manual before starting the unit
for the first time. It contains
useful tips and notes as well as
hazard warnings to prevent injury
or material damage
!
. Failure
to follow the directions in this
manual not only presents a danger
to people, the environment and
the system itself, but will void any
claims for liability.
Keep this operating manual and
the refrigerant data sheet near
to the unit.
The units and components
should be set up and installed
only by qualified personnel.
The set-up, connection,
and operation of the unit and its
components must take place in
accordance with the operating
conditions stipulated in this
manual and comply with all
applicable local regulations.
Mobile units must be set up
securely on suitable surfaces and
in an upright position. Stationary
units must be permanently
installed for operation.
Modification of units and
components supplied by
REMKO is not permitted and
can cause malfunctions.
Units and components may
not be operated in areas where
there is an increased risk of
damage. Observe the minimum
clearances.
The electrical supply is to be
adapted to the requirements
of the units.
The operational safety of
the units and components
is only assured if they are
fully assembled and used as
intended. Safety devices may
not be modified or bypassed.
Do not operate units or
components with obvious
defects or signs of damage.
All housing parts and openings
in the unit, e.g. air intakes and
outlets, must be free of foreign
objects, fluids, or gases.
The units and components must
be kept at an adequate distance
from flammable, explosive,
combustible, abrasive and dirty
areas or atmospheres.
Contact with some parts of the
unit or components can result in
burns or other injuries.
Installation, repair and
maintenance work may be
carried out by authorised
specialists only. Visual
inspections and cleaning can
be performed by the operator as
long as power is disconnected
from the equipment.
To preclude any danger from the
unit, take appropriate hazard-
prevention measures when
performing installation, repair or
maintenance work or cleaning
the unit.
The units and components
should not be exposed to any
mechanical load, extreme levels
of humidity or direct exposure
to sunlight.
Warranty
In order to make warranty claims, it
is essential that the ordering party
or their representative complete
and return the "certificate of
warranty" to REMKO GmbH
& Co. KG at the time when the
equipment is purchased and
commissioned.
The warranty conditions are
detailed in the "General business
and delivery conditions".
Furthermore, only the parties to
a contract can conclude special
agreements beyond these
conditions. In this case, first contact
your contractual partner.
Disposing of packaging
All products are carefully packaged
using environmentally friendly
materials prior to transportation.
You can make a valuable
contribution to reducing waste
and sustaining raw materials by
only disposing of packaging at
approved collection points.
Environmental
protection
and recycling
REMKO BL
4
The BL 261 and BL 351 room air
conditioning units have a REMKO
BL...AT outdoor component as
well as a BL...IT indoor unit.
The outdoor component serves to
output the heat extracted by the
indoor unit from the room being
cooled.
In heater operation, the heat taken
up by the outdoor unit can be
discharged by the indoor unit into
the room to be heated.
The outdoor component can be
installed outdoors or indoors.
The latter requires the fulfilment of
certain conditions. The indoor unit
is designed to be mounted high up
on indoor walls. It is operated by
an infrared remote control.
The outdoor component consists of
a cooling circuit with compressor,
fin condenser, condenser fan,
reverse flow valve, quick-release
couplings and throttle element.
The outdoor component is
controlled by the controller in the
indoor unit.
The indoor unit consists of a fin
vaporiser, vaporiser fan, controller
and condensation tray.
Floor consoles, wall consoles and
condensation pumps are available
as accessories.
System description
The units are delivered in strong
transport packaging. Immediately
check the units on delivery and
make a note of any damage or
missing parts on the delivery note.
Inform the forwarding agent and
contractual partner.
No warranty can be assumed for
later claims.
Transportation and
packaging
Cooling circuit diagram for indoor unit
Vaporiser fan
Suction line connection
with quick-release coupling
Injection pipe connection
with quick-release coupling
Vaporiser
The connection between the indoor unit and outdoor component is effected
using the factory-supplied refrigerant pipes by means of quick-release couplings.
Outdoor component
System configuration
Injection pipe
Indoor unit
Indoor area
Outdoor area
Shut-off valve with
quick-release coupling
Condenser fan
Condensate line
Suction line
Condensate line
Control cable
Mains cable
M
M
Cooling circuit diagram for the outdoor component
Condenser fan
Quick-release
coupling
connection valve
Suction line
Quick-release
coupling
connection valve
Injection pipe
Compressor
Capillary tube throttle elementFilter dryerCondenser
Reverse flow valve
Connection for
pressure gauge
5
Display on indoor unit
The display illuminates according to the settings.
max. 6 m
max. distance 6 m
Display on indoor unit
Timer
Automatic mode
Fan speed
Display
of coded error
messages, room and
target temperature
Cooling mode
Swing mode
Sleep function
Dehumidification mode
Temperature unit
Heating mode
Operation
Infrared remote control
The infrared remote control
sends the programmed settings
a distance of up to 6 m to the
receiver of the indoor unit.
Data will only be received correctly
if the remote control is pointed
at the receiver and no objects are
obstructing the transmission path.
First insert the supplied batteries
(2 each, type AAA) into the remote
control. To do so, remove the flap
from the battery compartment and
insert the batteries the correct way
around (see markings).
The indoor unit is easy to operate using an infrared remote control. This is supplied as standard. The indoor unit
beeps to acknowledge the correct transmission of data. If it is not possible to program the indoor unit using the
remote control, it can also be operated manually.
Problems are shown in code
(see Troubleshooting and
Customer service section).
! ATTENTION
Immediately replace flat
batteries with a new set,
otherwise there is a risk of
leakage.
It is recommended that the
batteries are removed if the
equipment is shut down for
long periods.
NOTE
Manual mode
The indoor units can be
commissioned
manually. After the air inlet screen
has been opened, the inner
recessed key can be pressed and
automatic mode can be activated.
In manual operation, the following
settings apply:
Cooling mode: last setting
Fan speed: AUTO
Heating mode: last setting
Fan: AUTO
Press a key on the infra-red
remote control to interrupt manual
operation.
Help save on energy consump-
tion in stand-by mode! If the
device, system or component
is not in use, we recommend
disconnecting the power sup-
ply. Components with a safety
function is excluded from our
recommendation!
TIP
REMKO BL
6
"TIMER OFF" key
Press this key to program the
automatic switch-off time
of the unit within the next
24 hours.
"HR" key
Press this key to set the hours.
"MIN" key
Press this key to set the
minutes.
"RESET" key
(in battery compartment)
Press this key to reset the
remote control to its factory
settings.
"CLOCK" key
(in battery compartment)
Press this key to activate the
time setting.
"DISPLAY" key
Press this key to switch the
display on and off (no influence
on device functionality)
Keys on the remote control 2. Cooling mode
In this mode, the warm air in
the room is cooled down to the
desired temperature.
3. Dehumidification mode
In this mode the room is mainly
dehumidified and the adjusted
temperature is maintained.
4. Heating mode
In this mode, the warm air in
the room is warmed to the
desired temperature.
"FAN" key
Press this key to set the
desired fan speed. 4 speeds
are available: Automatic, high,
medium and low fan speed.
"FINS" key
Press this key to set the desired
fin position. 5 positions and
an oscillating are function
available.
"SLEEP" key
Press this key to automatically
increase or decrease the target
temperature by 1°C every hour
in cooling and heating mode
respectively.
"SWING" key
Press this key to directly
activate the oscillating function
of the fins for better air
distribution in the room.
"TIMER ON" key
Press this key to program
the automatic activation time
of the unit within the next
24 hours.
Keys on the remote control
"ON/OFF" key
Press this key to operate the
unit.
"TOO HOT" key
Press this key to decrease
the desired temperature to
16°C.
"TOO COLD" key
Press this key to increase the
desired temperature to 31°C.
"MODE" key
Press this key to select the
operating mode.
The indoor unit has 4 modes:
1. Automatic mode
In this mode, the unit works in
cooling or in heating mode.
7
The remote control standby mode is signalled by the blinking dot on the
remote control.
Stand by of remote control
RESET key The remote control can be reset by pressing the RESET key in the battery
compartment. The time can then be programmed (see "CLOCK key").
RESET 5 sec. Setting the clock
The time can be programmed by pressing the CLOCK key inside the
battery compartment. "CLOCK" blinks in the display and the current
time is set via the HR. and MIN. key. Programming is completed by
pressing the CLOCK key again. The display will stop blinking.
CLOCK Key
CLOCKHR/MINCLOCK
Your air conditioner is activated and deactivated by pressing the ON /
OFF key. The programmed settings and adjustment values from before
the unit was turned off will appear on the display.
ON/OFF key
ON/OFF ON/OFF
A symbol is shown on the display to indicate that the settings are being transferred.
Key functions
REMKO BL
8
▲/▼ Keys The key can be used to reduce the desired target temperature, the
key can be used to increase it. In automatic mode, the temperature
can be increased or decreased by 1°C. In dehumidification mode, no
temperature adjustment can be made.
Cooling mode
The display turns off
after 1 min.
Automatic mode
MODE key Use the MODE key to switch between individual operating modes. A to-
tal of 4 modes are available:
1. Automatic cooling or heating operation
2. Cooling primarily summer mode
3. Dehumidifying operating mode for summer or winter
4. Heating mainly a winter operating mode
MODEMODEMODE
Automatic Cooling Dehumidification Heating
In automatic mode, the controller autonomously selects between heating
and cooling operation when the unit is first switched on. The control
range lies between 22°C and 26°C. This can be increased or decreased
with the ▲/▼ keys.
AUTOMATIC MODE
AUTOMATIC
MODE
In cooling mode, the air in the room is cooled to the set target
temperature. The desired room temperature is set with the ▲/▼ keys
in 1°C increments. If the room temperature is 0.5°C above the selected
target temperature, then the interior unit starts to cool the air in the
room. If the temperature falls to approx. 1°C below the set room
temperature, the controller will switch off cooling mode. To protect the
compressor, the controller only turns cooling on again after a wait time of
3 minutes.
COOLING mODE
COOLING
MODE
MODE
9
HEATING mode In heating mode, you can heat the room in spring or autumn. The
selected room temperature is set with the ▲/▼ keys in 1°C increments.
If the room temperature is 1°C below the selected target temperature,
the indoor unit will start to heat the air in the room. If the set room
temperature is exceeded by approx. 1°C, the controller will switch off
heating mode. To protect the compressor, the controller will wait 3
minutes before switching on the heating mode again.
MODE
HEATING MODE
In dehumidification mode, the target temperature is set to 24°C. Due to
the low temperature of the refrigerant, the temperature of the air at the
condenser falls below the dew point. The excess moisture in the air is
condensed by the vaporiser, the room is dehumidified. The fan speed
is permanently set to the lowest setting in order to achieve a maximum
level of dehumidification. The compressor switches on and off in intervals
between 17°C and 24°C.
DEHUMIDIFICATION MODE
DEHUMIDIFICATION
MODE
MODE
The fan speed can be adjusted with this key. A selection can be made
between low, medium, high and automatic fan speed.
FAN Key
FANFANFAN FAN
The air discharge fins are individually adjusted with this key.
A selection can be made between 5 positions and an oscillating function.
FINS Key
The oscillating function of the air fins can be adjusted with this key.
This makes it possible to switch directly between a preset position and
the oscillating function. The air distribution in the room is improved with
the swing function.
SWING key
SWINGSWINGSWING
REMKO BL
10
TIMER Key
The activation and switch-off time can be programmed with this key.
The timer is activated and the clock display is switched off by pressing
the Timer On or Timer Off keys. The timer symbol for the switch-on/
off time will flash. The timer display on the indoor unit illuminates.
The desired switch on or switch off time is set by pressing the keys HR.
and MIN. Following adjustment, the timer symbol blinks for another
30 seconds. When the programmed time has been reached, the unit
automatically switches on or off. If the indoor unit is automatically
switched on, the mode, temperature and fan speed for the last setting
are activated. The switch on/off time can be prematurely cancelled by
pressing the appropriate timer key or the ON/OFF key. The timer display
on the indoor unit turns off.
TIMER Key ON
Timer on HR/MIN 30 sec.
TIMER Key OFF
Timer off HR/MIN 30 sec.
A programming function is activated with this key, which increases the
target temperature in cooling mode by 1°C after one hour and by 2°C
after 2 hours. In heating mode, the target temperature is decreased
by 1°C after one hour by 2°C after 2 hours. The unit switches off
automatically after 8 hours.
SLEEP Key
TIMER Key ON/OFF
Unit On Unit Off
Example:
The controller turns on at 10:20.
The unit is in operation until 05:00.
The controller turns the unit on and off daily at the programmed time.
During operation, all settings and the timer symbol can be seen on the
display. When not in operation, the display 0->1 and the timer symbol
can be seen.
SLEEPSLEEPSLEEP
11
There are individually adjustable
fins for adjusting the horizontal air
distribution on the air discharge
side.
Manual air distribution
Moving interior parts such as
the fan may to cause injury
during operation!
Only make adjustments after
swing operation has been
turned off.
! ATTENTION
Shift lever left
Manual air distribution
Shift lever right
Decommissioning
Temporary
Decommissioning
1. Let the indoor unit run for 2
to 3 hours in circulation mode,
or in cooling mode at maximum
temperature, to extract any
residual humidity from the unit.
2. Shut down the system using the
remote control.
3. Switch off the voltage supply to
the unit.
4. Cover the unit as far as possible
with plastic foil in order to
protect it from the influences of
weather.
Care and maintenance
Regular care and maintenance
ensure the trouble-free operation
and long service life of the unit.
Care
Ensure that the indoor unit
and outdoor component are
protected against dirt, mould
and other deposits.
Clean the units with a damp
cloth. Do not use any caustic,
abrasive or solvent-based
cleaning products. Do not use
a jet of water.
Clean the fins on the indoor
unit and outdoor component
prior to long shutdown periods.
Prior to performing any work,
ensure that the equipment
is isolated from the voltage
supply and secured to prevent
accidental switch-on!
! ATTENTION
Permanent
decommissioning
Ensure that equipment and
components are disposed of in
accordance with local regulations,
e.g. through authorised disposal
and recycling specialists or at
collection points.
REMKO GmbH & Co. KG or your
contractual partner will be pleased
to provide a list of certified firms in
your area.
REMKO BL
12
Maintenance
It is recommended that you
take out a maintenance
contract with an annual service
from an appropriate specialist
firm.
Cleaning of condensation
pump (optional equipment)
An optional integrated or separate
condensation pump may be in the
indoor unit, which pumps out any
accumulated condensation into
higher positioned drains.
Observe the care and maintenance
instructions in the separate
Operating Instructions.
Type of task
Checks/Maintenance/Inspection
Commissioning
Monthly
Half-yearly
Yearly
General
Measure voltage and current
Check function of compressor/fans
Check function of fan
Dirt on condenser/vaporiser
Check refrigerant fill quantity
Check condensate drain
Inspect insulation
Check moving parts
Sealing test for cooling circuit 1)
Cleaning the housing on
the indoor unit
1. Disconnect the supply voltage
to the equipment.
2. Open and fold the air inlet
guard on the front side
upwards.
3. Clean the guard and cover with
a soft, damp cloth.
4. Switch the supply voltage back
on.
Air filter for indoor unit
Clean the air filter at intervals of
no more than 2 weeks.
Reduce this interval if the air is
especially dirty.
Cleaning the filter on
the indoor unit
1. Disconnect the supply voltage
to the equipment.
2. Open the front side of the unit
by folding the guard upwards
and allowing it to engage
(figure 1).
3. Raise the filter and pull it out
pulling downwards.
2 Cleaning using a vacuum cleaner
3
Cleaning with lukewarm water
This ensures the operational
reliability of your system!
TIP
4. Clean the filter with
a commercially available
vacuum cleaner. Turn the dirty
side upwards (figure 2).
5. Dirt can also be removed
by carefully cleaning with
lukewarm water and mild
cleaning agents. Turn the dirty
side downwards (figure 3).
6. If water is used, let the filter dry
out properly in the air before
fitting it back into the unit.
7. Carefully insert the filter. Ensure
that it locates correctly.
8. Close the front side as
described above in reverse
order.
9. Switch the supply voltage back
on.
10.
Switch the unit on again.
1 Fold the guard upwards
13
Troubleshooting and customer service
The units and components are manufactured using state-of-the-art production methods and tested several
times to verify their correct function. However, if malfunctions should occur, please check the functions as
detailed in the list below. Please inform your dealer if the unit is still not working correctly after all function
checks have been performed!
Fault Possible cause Checks Remedial measures
The unit does not start or
switches itself off.
Power outage, undervoltage,
defective mains fuse / main switch
in OFF position
Are all electrical
installations functioning correctly?
Check the voltage and
if necessary, wait for it to come
back on
Damaged mains cable Are all electrical
installations functioning correctly? Repair by specialist
Wait time after switching on is
too short
Have approx. 5 minutes
elapsed since the restart? Schedule longer wait times
Working temperature fallen below
/ exceeded
Are the fans in the indoor unit
and outdoor component working
correctly?
Take into account the temperature
range for the indoor unit and
outdoor component
Electrical surges caused by
thunderstorms
Have there been lightning strikes
in the area recently?
Switch off the mains protection
and switch it back on /
have it checked by a specialist
Fault in external
condensation pump
Did the pump shut down due to
a fault?
Check and if necessary clean the
pump
The unit does not respond
to the remote control.
Transmission distance too far /
receiver affected by interference
Does the indoor unit beep when
pressing a key?
Reduce the distance to less than
6 m or change position
Defective remote control Is the unit running in manual
mode? Replace the remote control
Receiver or transmitter unit
exposed to excessive solar
radiation
Does it function correctly in the
shade?
Place the receiver and/or
transmitter unit in the shade
Electromagnetic fields are
interfering with transmission
Does it function after removing
potential sources of interference?
Signal is not transmitted when
sources of interference are
operational
Key in remote control jammed /
two keys pressed at same time
Does the “Send” symbol appear
on the display?
Release the key / only press one
key
Batteries in remote control are flat Have new batteries been inserted?
Is the display incomplete? Insert new batteries
The unit is running but
only provides reduced or no
cooling or heating
performance.
Filter is unclean / air intake /
outlet blocked by foreign objects Have the filters been cleaned? Clean the filters
Doors and windows open.
Heating/cooling output increases
Have structural /
usage modifications been made?
Close windows and doors / install
additional units
Neither cooling nor heating mode
has been set
Is the cooling/heating symbol
shown on the display? Correct the settings for the unit
Fins on outdoor component
blocked by foreign objects
Is the fan on the outdoor
component running? Are the fins
unobstructed?
Check the fan or winter controller,
reduce the air resistance
Leaking cooling circuit Are there signs of frost on
the fins of the indoor unit?
Repair by specialist
Condensate is leaking out
Drainage pipe on collection
container clogged / damaged
Is unrestricted condensate
discharge ensured?
Clean the drainage pipe and
collection container
Faulty external condensation
pump or float
Is the condensation tray full and
the pump running?
Call out a specialist to replace the
pump
Condensation has collected in the
condensate line
Has the condensate line been
laid on an incline and is it
unobstructed?
The condensate line must be on
an incline. If necessary, clean the
line
Condensate does not drain off
Are the condensate lines unblocked
and is there a steady incline?
Are the condensation pump and
float switch functioning correctly?
Install the condensate line on
an incline and clean if necessary
/ if the float switch or the
condensation pump is defective,
have them replaced
Malfunctions
REMKO BL
14
Fault indication by flashing code
Display Cause Required action
E1 Indoor unit probe air circulation defective Contact specialist dealer
E2 Indoor unit probe frost protection defective Contact specialist dealer
E4 Cooling mode: No cooling output after 30 minutes
Heating mode: No heating output after 30 minutes Contact specialist dealer
E5 Cooling mode: Frost protection has responded
Heating mode: Overheating protection has tripped Contact specialist dealer
E6 Bridge inner control cable interrupted Check bridge plug
15
Installation instructions for qualified personnel
Important notes prior to
installation
Transport the unit in its original
packaging as close as possible
to the installation location.
This helps to prevent damage
during transportation.
Check the contents of the
packaging for completeness
and check the unit for visible
transport damage. Report any
damage immediately to your
contractual partner and the
shipping company.
Lift the unit on the corners and
not on the refrigerant
or condensate connections.
The refrigerant pipes
(injection and suction line),
valves and connections must be
insulated impervious to vapour
diffusion. If necessary, also
insulate the condensate line.
Select an installation location
which allows air to flow
freely through the intake and
outlet (see section "Minimum
clearances").
Do not install the unit in the
immediate vicinity of devices
which generate intensive
thermal radiation. Installation
near sources of thermal
radiation reduces the output of
the unit.
Only open the shut-off valves
of the refrigerant pipes after
installation is complete.
Seal off open refrigerant lines
with suitable caps or adhesive
strips to prevent the infiltration
of moisture and never kink or
compress the refrigerant pipes.
Avoid unnecessary bends.
You thereby minimise loss of
pressure in the refrigerant pipes
and ensure clear return flow of
the compressor oil.
Take special precautions with
regard to the oil return if
the outdoor component is
located above the indoor unit.
See section "Oil return flow
measures".
Only use the refrigerant pipes
provided in the delivery and
only removethe protective caps
shortly before connection to the
outdoor component.
Make all electrical connections
in accordance with applicable
DIN and VDE standards.
Always attach electrical lines
properly in electrical clamps,
otherwise a fire could result.
Both units and the extension
lines are pre-filled with
refrigerant.
Suitable protective
clothing
must be worn during
installation
.
! ATTENTION
REMKO BL
16
Selection of installation location
Indoor unit
The indoor unit is designed for
horizontal wall installation above
doors. However, it can also be
used in the upper wall area
(min. 1.75 m above the floor).
The indoor unit is not suitable for
installation on roof inclines.
Outdoor component
The outdoor component is
designed for horizontal installation
on a base in outdoor areas.
The installation site must be level,
flat and firm. The unit should also
be secured to prevent toppling.
The outdoor component can be
set up outside as well as inside
a building. For external installation,
please observe the following
notes to protect the unit from the
influence of the weather.
Rain
For attic or roof set up, the unit
should be installed with at least
10 cm ground clearance. A floor
bracket is available as an optional
accessory.
Sun
The condenser on the outdoor
component emits heat.
Exposure to direct sunlight will
further increase the temperature
of the fins and reduce the
heat output of the finned
heat exchanger. The outdoor
component should be installed on
to the north side of the building
whenever possible. If necessary,
take measures to provide sufficient
shade (responsibility of customer).
One possible solution is to build
a small roof. These measures
should not affect the flow of warm
outlet air.
Wall openings
A wall opening of at least
70 mm diameter and 10 mm
incline from the inside to the
outside must be made for each
indoor unit.
We recommend that the inside
of the opening is padded or
lined, e.g. using a PVC pipe,
to prevent the lines being
damaged.
After installation, the wall
opening should be closed off
with a suitable sealant. Do not
use materials containing cement
or lime!
Installation materials
The indoor unit is attached to
the wall by a wall bracket and
4 screws (to be provided by the
customer).
The outdoor component is
attached by 4 screws and a wall
bracket to the wall or fixed by
a floor bracket to the ground.
Windbreak
Wind
Lines in the wall opening
Control cable
Condensate line
Injection pipe
Suction line
PVC pipe
Wind
If the unit is being installed in
windy areas, ensure that the
warm outlet air discharges in the
prevailing wind direction. If this
is not the possible, it may be
necessary to install a windbreak
(to be provided by the customer).
Ensure that the windbreak does
not adversely affect the air intake
to the unit.
Snow
The unit should be wall-mounted
in areas of heavy snowfall.
Installation should then be at least
20 cm above the expected level
of snow to prevent snow from
entering the outdoor component.
An optional wall bracket is
available as an accessory.
Minimum clearance to snow
20 cm
Snow
17
200
120
1500
120
120
Minimum clearances
E
C
B
A
D
Air intake
Air outlet
Air intake
Air outlet
All dimensions are given in mm
Installation inside buildings
Ensure that heat can dissipate
adequately when placing the
outdoor component in cellars,
lofts, adjoining rooms or halls
(figure 4).
Install an additional fan with
a rated flow comparative to
that of the outdoor component
being installed in the room
and which can compensate
any additional pressure loss in
ventilation ducts (figure 4).
Ensure a continuous and
unobstructed air flow from
outside, preferably using
sufficiently large air intakes
placed opposite each other
(figure 4).
Minimum clearances
Observe the minimum clearances
to allow access for maintenance
and repair work and facilitate
optimum air distribution.
BL 261 AT, BL 351 AT
A 150 mm
B 700 mm
C 400 mm
D 150 mm
E 200 mm
Comply with any regulations
and conditions affecting
the statics of the building.
If necessary, fit acoustic
installation.
Warm air Fresh
cold air
Light
well
Outdoor component
Warm air
Light
well
additional
fan
4 Installation inside buildings
REMKO BL
18
Connections
1 Outlet on the wall, right
2 Outlet through the wall, right
3 Outlet through the wall, right
4 Outlet on the wall, left
12
34
Connections
on the indoor unit
Both units are pre-filled with
refrigerant.
Suitable protective
clothing
must be worn during
installation
.
! ATTENTION
Connection lines are filled with
refrigerant! Suitable protective
clothing must be worn during
installation
.
! ATTENTION
Unit installation
The indoor unit is attached by
means of a wall bracket, taking
into consideration the air discharge
side located in the lower part.
1. Mark the mounting points on
the structurally permissible
building sections according
to the dimensions of the wall
bracket.
2. If necessary, remove the break
out opening of the housing.
3. Connect the refrigerant pipes
to the indoor unit as described
below. The flexible refrigerant
pipe and the electrical control
cable are pre-installed.
4. Suspend the indoor unit on the
wall bracket by tilting it back
slightly and then by pressing
the bottom part of the unit
against the bracket (figure 5).
5. Check again that the unit is
level.
Wall bracket
for indoor unit
The wall bracket for the unit must
be attached with suitable screws
and anchors.
Installation
Installation should only be
performed by authorised
specialists.
NOTE
Oil return measures
If the outdoor component is
installed at a higher level than
the indoor unit, suitable oil return
measures must be taken. Usually,
an oil pump bend is installed
for every 2.5 metres of height
difference.
Connection of
refrigerant pipes
The refrigerant pipes should be
connected by the customer on the
right-hand side of the outdoor
component.
1.
Use the wall or floor brackets to
fasten the outdoor component
where structurally allowed
(refer to the installation
instructions for the brackets).
2.
Ensure that structure-borne
sound is not transferred to
the building. Use vibration
dampers to reduce the effects
of structure-borne sound!
3.
Prepare the refrigerant pipes
for the outdoor component as
described above.
5
Connecting
Extending the
refrigerant pipes
The 2 m refrigerant pipe contained
in the delivery may be extended by
3 metres or 8 metres.
1.
Remove the protective caps
from the quick connectors.
2. Connect the suitable pipes and
check their leak tightness after
connection.
19
Oil return measures
Outdoor component
Oil pump bend
in suction line
to outdoor
component one
every 2.5 metres of
height difference
Radius:
Min. 100 mm
Max. 2.5 m
Indoor unit
Connection of quick-
release couplings
The refrigerant pipes should be
connected by the customer on the
right-hand side of the outdoor
component.
The pre-filled refrigerant pipes
are connected to the outdoor
component by means of the quick-
connector system. Once installed,
the connections must be insulated
to prevent vapour diffusion.
The following instructions describe
the installation of the refrigerant
pipes of the indoor unit to the
outdoor component.
1.
Remove the pre-installed
plastic cover from the outdoor
component (figure 6).
2. Remove the white protective
caps from the quick-connectors
on the outdoor component,
as well as the flexible
refrigerant pipes on the indoor
unit (figures 7 and 8).
3. Before connecting the
refrigerant pipes, ensure that
the quick-release couplings are
situated in front of one another
(figure 9).
4. First connect and hand-tighten
the refrigerant pipes to ensure
they are correctly seated.
5. Then install the suction line
with the largest diameter
(figure 10).
6. Now fully tighten the fittings
using 2 suitably sized open-
ended spanners. Use one
spanner to counter the force
when tightening the fitting
(figure 11).
7. Open the stop cocks before
turning on the system using an
Allen key!
Additional notes for installation
The flexible refrigerant pipes
supplied can be extended by
3 metres or 8 metres.
The flexible extension lines are
pre-filled with refrigerant.
Only use tools and
components designed for
refrigeration applications.
NOTE
Only open the stop
cocks following complete
installation of the quick-
release couplings and
before turning on the system!
NOTE
10 Installation of suction line
6 Remove the plastic cover
9
Connect the quick-release couplings
7 Remove the protective caps
8 Remove the protective caps
Tighten
1st spanner
Counter with
2nd spanner
11 Tightening fittings
Tightening
torque:
14
15-20 Nm
38
33-40 Nm
12
50-60 Nm
58
65-75 Nm
34
95-105 Nm
Installation should only
be performed by certified
specialists.
NOTE
REMKO BL
20
10
Incline of the condensate line
minimum
2% incline
The condensate hose is designed
to be connected on the left-hand
side (as viewed from the front).
All electrical installation
work should be performed
by specialist contractors.
Disconnect the power supply
when connecting the electrical
terminals.
! ATTENTION
Leak testing
Pumping down to
vacuum
Once all the connections have
been made, the pressure gauge
station is attached to the Schrader
valve as follows (if fitted):
red = small valve
= injection pressure
blue = large valve
= suction pressure
Following connection of the quick-
release couplings, the connections
are checked using leak detection
spray and suitable devices for leak-
tightness. If leaks are found, the
connections have not been made
properly. Tighten the connection
or, if necessary, remove the quick-
release coupling and check for
contamination or damage.
A vacuum of min. 20 mbar
must be created!
! ATTENTION
The time required to generate the
vacuum is dependent on the
pipe volume of the indoor unit
and the length of the refrigerant
pipes. This always takes at least
60 minutes.
Once any foreign gases and
humidity have been completely
extracted from the system, the
valves on the pressure gauge
station are closed and the valves
on the outdoor component
are opened as described in the
"Commissioning" section.
Electrical connection
A mains cable must be installed
as voltage supply and a control
cable to the indoor unit. The air
conditioning unit should be fused
in accordance with the technical
data. The pre-installed control
cable on the indoor unit must be
laid to the outdoor component.
We recommend installing
a main / repair switch on the
building close to the indoor
unit.
If an optionally available
condensation pump is used
on the unit, then an additional
relay for the shut-off contact
of the pump will be needed
to increase the switching power
to shut off the compressor.
Both units are pre-filled with
refrigerant. Pumping down to
vacuum is not required before
first commissioning.
! ATTENTION
Condensate draining and
ensured discharge
Condensate connection
If the temperature falls below the
dew point, condensation will form
on the finned condenser during
heating operation.
A condensate drip pan should be
installed on the underside of the
unit to drain any condensate.
The condensate drain pipe to
be installed on-site must be in-
stalled with a in cline of at least
2 % for good drainage.
If necessary, fit vapour density
insulation.
When operating the system at
outdoor temperatures below
4 °C, care must be taken that
the condensate line is frost
protected. The lower part of the
housing and condensate pan
are to be kept frost free in order
to ensure permanent drainage
of the condensate.
If necessary, fit supplementary
pipe heating.
After completed installation,
check that the condensate
drainage is unobstructed and
ensure that the line is leak tight.
Ensured discharge in the event of
leakage
Local regulations or environmen-
tal laws, for example the German
Water Resource Law (WHG), can
require suitable precautions to pro-
tect against uncontrolled draining
in case of leakage to provide for
safe disposal of escaping refrigera-
tor oil or hazardous media.
21
Neutral conductor
Fan motor (white)
Control cables should be
screened if laid in areas exposed
to strong magnetic fields.
Details concerning the electrical
protection of the system are
provided in the technical data.
Connection of the outdoor
component
Proceed as follows to connect the
cable:
1. Remove the cover from the
unit.
2. Remove the side panel next to
the terminals.
3. Feed the control cable through
the edge protection rings on
the fixed connection panel.
5. Insert the connector into the
corresponding socket.
6. Anchor the cable in the strain
relief and re-assemble the unit
(figure 12).
Check all plugged and clamped
terminals to verify they are
seated correctly and make
a permanent contact. Tighten
as required.
! ATTENTION
12
Connection of the outdoor component
Connecting the indoor unit
2 a 10 m long control cable are
already connected to the indoor
unit. These control cables must be
laid to the outdoor component and
connected to the terminal block.
Electrical connection diagram
Connection of BL 261, BL 351
11
Connection of the indoor unit
Front terminal for
control cable to outdoor
component
Cover
Rear terminal for
electrical supply
Cover
Outdoor component
Indoor unit Mains cable
Reverse flow valve (black)
230 V~,
50 Hz,
L1 / N
/ PE
Compressor contact (red)
PE
NN
PE
3
2
3
PE
N
L L L
2
11
Exterior conductor
rear
terminal
front
terminal
REMKO BL
22
Electrical drawings
BL 261, BL 351 IT
BL 261, BL 351 AT
R
S
L
N
3
2
1
C
BK
BU
BU
BK
WH
BN
BU
Condenser fan
Compressor
Compressor contact Colour code
WH = white
BU = blue
BR = brown
BK = black
Reverse flow valve
3
1
2
L
NAC-N
FM SM
AC-L
COMP
Display
Receiver
Probe vaporiser Probe air circulation
Vaporiser fan motor Swing motor
Trans-
former
Exterior conductor
Neutral conductor
Earth conductor
Condenser fan (white)
Reverse flow valve (black)
Compressor (red)
Exterior conductor
Neutral conductor
Earth conductor
Condenser fan (white)
Reverse flow valve (black)
Compressor (red)
23
Adding refrigerant
The units contain a basic
quantity of refrigerant. Should
the refrigerant leak, remedy
the leak, pump the refrigerant
pipes down to a vacuum and refill
the basic quantity of refrigerant.
Refrigerant fill
quantity BL 261 BL 351
Basic
line length 0.7 kg 1.0 kg
Following a successful leak check,
the unit can be started again
without the pipes needing to be
pumped down to a vacuum.
Perform the following checks
prior to commissioning the unit
for the first time and after any
interventions affecting the cooling
circuit. Record the results in the
commissioning report:
Check and open shut-off valves
Check all refrigerant pipes and
valves using leak detection
spray or soapy water to ensure
they are tight and that the
suction and injection pipes have
not been accidentally confused
with the unit at a standstill.
Check the refrigerant lines and
insulation for damage.
Check the electrical connection
between the indoor unit and
the outdoor component for
correct polarity.
Check that all fastenings,
mountings etc. are firm and at
the correct level.
Before
commissioning
When filling the system with
refrigerant, ensure that it is
always in liquid form!
! ATTENTION
NOTE
Check overheating to
determine the refrigerant fill
quantity.
Wear protective clothing when
handling refrigerant.
! ATTENTION
Commissioning
Commissioning should only be
performed and documented
by specially trained personnel.
NOTE
The system can be commissioned
once all the components have
been connected and tested.
A functional check should be
performed to verify its correct
function and identify any unusual
operational behaviour prior to
handing it over to the operator.
Functional checks and
test run
Check the following points:
Leak tightness of refrigerant
pipes.
Compressor and fan running
smoothly.
In cooling mode, cold air
output by the indoor unit, and
warm air output by the outdoor
component.
Functional test of the indoor
unit and all program sequences.
Check of the surface
temperature of the suction
line and check vaporiser is
not overheating. To measure
the temperature, hold the
thermometer to the suction
line and subtract the boiling
point temperature reading on
the pressure gauge from the
measured temperature.
Record the measured
temperatures in the
commissioning report.
NOTE
The escape of refrigerant con-
tributes to climatic change. In
the event of escape, refrigerant
with a low greenhouse poten-
tial has a lesser impact on glo-
bal warming than those with a
high greenhouse potential.
This device contains refrige-
rant with a greenhouse poten-
tial of 1975. That means the
escape of 1 kg of this refrige-
rant has an effect on global
warming that is 1975 times
greater than 1 kg CO2, based
on 100 years. Do not conduct
any work on the refrigerant
circuit or dismantle the de-
vice - always enlist the help of
qualified experts.
REMKO BL
24
Function test of the cooling
and heating modes
1. Remove the protective caps
from the valves.
2. Start the commissioning
procedure by briefly opening
the shut-off valves on the
outdoor component until
the pressure gauge indicates
a pressure of approx. 2 bar.
3. Use leak detection spray or
suitable devices to check that all
the connections are tight.
Final tasks
Reassemble all disassembled
parts.
Familiarise the operator with
the system.
4. If no leaks are found, fully open
the shut-off valves by turning
them anti-clockwise using a
spanner. If leaks are found,
remedy the faulty connection.
It is imperative that the vacuum
creation and drying steps are
repeated!
5. Switch off the main circuit
breaker or remove the fuse (to
be provided by the customer).
6. Use the remote control to
switch on the unit and select
the cooling mode, maximum
fan speed and lowest target
temperature.
7. Measure and record all
the required values in the
commissioning report and
check the safety functions.
8. Check the indoor unit control
system using the functions
described in the "Operation"
section. Timer, temperature
setting, fan speeds and
switching to ventilation or
dehumidification mode.
9. Check the correct function
of the condensate line by
pouring distilled water into the
condensation tray.
A bottle with a spout is
recommended for pouring the
water into the condensation
tray.
10.
Switch the indoor unit to
cooling mode.
11.
Check the correct function
and settings of all regulation,
control and safety devices
during the test run.
12.
Check the control system in the
indoor unit using the functions
described in the Operating
Manual.
Timer, temperature settings and
all mode settings.
13.
Check the overheating,
outdoor, indoor, outlet and
vaporisation temperatures and
record the measures values in
the commissioning report.
14.
Switch the indoor unit to
heating mode.
15.
Check the functionality of all of
the previously described safety
devices and during the test run.
16.
Record the measured values in
the commissioning report.
17.
Remove the pressure gauge.
Check that seals have been
fitted in the sealing caps.
Check that the shut-off
valves and valve caps are
tight after carrying out any
work on the cooling circuit.
Use appropriate sealant
products as necessary.
NOTE
25
Unit dimensions
We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
All dimensions are given in mm
BL 261, BL 351 AT
780
510
280
250
540
790
275
BL 261, BL 351 IT
200
REMKO BL
26
Exploded view of BL 261 IT, BL 351 IT
We reserve the right to modify the dimensions
and constructional design as part of the ongoing technical development process.
When ordering spare parts, please state the EDP no., unit number and unit type (see identification plate)!
Spare parts list
No. Designation BL 261 IT BL 351 IT
From serial number 801D51-... 807D51-...
1 Front panel, complete 1109400 1109413
2 Air filter, set 1109453 1109414
3 Circuit board, display 1109402 1109415
4 Swing motor 1109403 1109416
5 Air outlet fins, set 1109404 1109417
6 Condensation tray 1109405 1109418
7 Vaporiser 1109454 1109459
8 Fan wheel 1109407 1109420
9 Fan motor 1109455 1109421
10 Control board 1109480 1109481
11 Transformer 1109410 1109423
12 IR remote control 1109411 1109424
Spare parts not illustrated
Probe air circulation / vaporiser 1109412 1109425
Injection pipe quick-release couplings 1109457 1107873
Suction line quick-release couplings 1109458 1107874
3
1
2
7
4
8
9
11
12
6
10
5
27
REMKO BL
28
No. Designation
BL 261 AT BL 351 AT
From serial number 801D81-... 807D81-...
1 Front panel 1107885 1107886
2 Fan blade, condenser 1107864 1107864
3 Fan motor, condenser 1107865 1107865
4 Finned condenser 1107936 1107937
5 Cover panel 1107934 1107935
6 Side panel, right 1107932 1107933
7 Compressor, complete 1107866 1107867
8 Condenser, compressor 1107807 1107820
9
Condenser, condenser fan
1107808 1107821
10 Shut-off valve, suction line 1107809 1107822
11 Shut-off valve, injection pipe 1107810 1107823
12 Compressor contact 1107811 1107824
13 Reverse flow valve 1107812 1107825
Spare parts not illustrated
Injection pipe quick-release coupling 1107878 1107871
Suction line quick-release coupling 1107879 1107872
Exploded view of BL 261 AT, BL 351 AT
6
1
2
4
5
Spare parts list
When ordering spare parts, please state the EDP no., unit number and type of unit (see identification plate)!
3
7
8
9
10
11
13
12
29
Technical data
Series BL 261 BL 351
Operating mode Wall / room air conditioner combination for cooling and heating
Nominal cooling output 1) kW 2.69 3.59
Nominal heating output 2) kW 2.96 4.24
Energy efficiency rating, cooling 1) A A
Energy efficiency ratio EER 1) 3.32 3.23
Energy efficiency rating, heating 2) A A
Energy efficiency ratio COP 2) 3.70 3.66
Power consumption, yearly, (500h) C/H kWh 405 / 400 555 / 580
Operating range (room volume), approx. 80 110
Refrigerant R 410A 4)
Operating pressure, max. kPa 4200 / 4200
Power supply V/Hz 230 / 1~ / 50
Nom. electrical power consumption, cooling 1) kW 0.81 1.11
Electrical rated power consumption, heating 2) kW 0.80 1.16
Electrical rated power consumption, cooling 1) A 3.60 4.99
Electrical rated power consumption, heating 2) A 3.61 5.32
Electr. starting current, max. A 21 28
Max. operating pressure kPa 4200 / 4200
Data specific to indoor unit BL 261 IT BL 351 IT
Adjustment range, room temperature °C +16 to +31
Operating range °C +15 to +31
Air flow volume per speed setting m³/h 320/370/420 380/450/520
Sound pressure level per speed setting 3) dB(A) 30/34/38 32/36/40
Protection class IP X0
Condensate draining mm 17 17
Dimensions - height mm 275 275
width mm 790 790
depth mm 200 200
Weight kg 8,0 10,0
Data specific to outdoor component BL 261 AT BL 351 AT
Operating range, cooling °C +7 to +48
Operating range, heating °C -7 to +25
Air flow rate, max. m³/h 1925 2050
Protection class IP 24
Sound pressure level, max. 3) dB(A) 52 53
Refrigerant, basic capacity kg 0.70 1.00
Refrigerant pipe, length approx.
series / accessories m 2 / 10
Refrigerant pipe, height, max. m 5
Dimensions - height mm 540 540
width mm 780 780
depth mm 250 250
Weight kg 30,0 34,0
Serial number 801... 807...
EDP no. 1630365 1630360
1) Air inlet temperature TK 27°C / FK 19°C, outdoor temperature TK 35°C, FK 24°C, max. air flow rate
2) Air inlet temperature TK 20°C, outdoor temperature TK 7°C / FK 6°C, max. air flow rate
3) Distance 1m free field
4) Contains greenhouse gas according to Kyoto protocol
EC – Declaration of Conformity
in accordance with the Machinery Directive, Annex II 1A
Original Declaration of Conformity
We hereby declare that the devices named below, produced and sold by us, satisfy the relevant
basic requirements of the EC guidelines, the EC safety standards and other product-specific EC
standards.
Name of Manufacturer: REMKO GmbH & Co. KG
Klima- und Wärmetechnik
Im Seelenkamp 12
D - 32791 Lage
Name of the CE representative: REMKO GmbH & Co. KG
Klima- und Wärmetechnik
Im Seelenkamp 12
D - 32791 Lage
Equipment (machinery) - Implementation:
Wall - room air conditioner combination in split
design with quick-release coupling system
Series / Designation: REMKO B
L 261, BL 351
Series / Class Number: 801..., 807...
Applicable regulations:
MA - RL 2006/42/EG Machinery Directive
NS - RL 2006/95/EG Low-voltage directive
EMV – RL 2004/108 EWG EMC Directive
EnVKV - RL 92/75/EWG Energy Consumption Labelling Directive
EG 97/23/EG Pressure Equipment Directive
Applicable Standards:
DIN EN ISO 12100-1-2 : 2004-04; DIN EN ISO 13857,
EN 14511 T1-4;
DIN 45635 - 1;
EN 378 – 1-4;
EN 55014 - 1; EN 55014 - 2; EN 55104
EN 60204 - 1; EN 60335 - 1; EN 60335 - 2 - 40;
EN 61000 - 3 - 2; EN 61000 - 3 - 3;
Lage, 22 January 2010 REMKO GmbH & Co. KG
..............................................
Signature, Product Manager
We reserve the right to make technical changes, and provide no warranty as to the accuracy of this data!
Consultation
Thanks to intensive training,
our consultants are always
completely up-to-date when
it comes to technical expertise.
This has given us the reputation
of being more than just an
excellent, reliable supplier:
REMKO, a partner, who helps
to solve problems.
Sales
REMKO offers not just a well
established sales network both
nationally and internationally,
but also has exceptionally highly-
qualified sales specialists.
REMKO field staff are more than
just sales representatives: above
all, they must advise our clients
in the areas of air conditioning
and heating technology.
Customer service
Our equipment operates
precisely and reliably. However,
in the event of a fault, REMKO
customer service is quickly on the
scene. Our comprehensive
network of experienced dealers
guarantees quick and reliable
service.
REMKO INTERNATIONAL
... and also right in your neighbourhood!
Benefit from our experience and advice
Hotline
Air conditioning and
heating technology
+49 5232 606-0
Export
+49 5232 606-130
REMKO GmbH & Co. KG
Klima- und Wärmetechnik
Im Seelenkamp 12 D-32791 Lage
Postfach 1827 D-32777 Lage
Telephone +49 5232 606-0
Fax +49 5232 606-260
E-mail info@remko.de
Internet www.remko.de
22


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO BL351 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO BL351 in the language / languages: English as an attachment in your email.

The manual is 4,4 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO BL351

REMKO BL351 User Manual - German - 28 pages

REMKO BL351 User Manual - German - 32 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info