Remeha
Gas 3002 ECO
Other messages Instructions
flue resistance high, check heat exchanger For the necessary air differential pressure a higher fan speed than normal is required.
preventive message see documentation This could indicate that boiler, flue gas discharge line and air intake pipe and/or siphon fouling.
Controlstop Instructions
boiler diff. temp. Boiler temperature differential is getting too high.
too high Check: - boiler/installation water flow
- boiler water level
- working pressure (min. 0.8 bar)
heat exch. temp. rise Boiler temperature rise faster than usual.
too fast Check: - boiler/installation water flow
- boiler water level
flow temp. rise too fast - working pressure (min. 0.8 bar)
flue gas temp. too high Flue gas temperature threatens to rise above the set maximum value.
Check: - the set maximum flue gas temperature (see par. 7.3.3, option no. 4)
Minimum setting: 15°C above maximum return water temperature
- boiler setting
- boiler fouling
main supply voltage Mains supply too low or too high.
too low Check mains supply.
main supply voltage Take off fan cable from cable channel
too high
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Gas 3002 ECO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Gas 3002 ECO in the language / languages: English as an attachment in your email.

The manual is 1,23 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Gas 3002 ECO

Remeha Gas 3002 ECO User Manual - German - 28 pages

Remeha Gas 3002 ECO Manual - Dutch - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info