Discharge Pipe work
It is a requirement of Building Regulations that any discharge from an unvented system is
conveyed to where it is visible, but will not cause danger to persons in or about the building. The
tundish and discharge pipes should be tted in accordance with the requirements and guidance
notes of Building Regulations. Building Regulation G3 Requirements and Guidance section 2
(page 17) are reproduced in the previous sections.
For discharge pipe arrangements not covered by G3 Guidance advice should be sought from
your local Building Control O󰀩cer. Any discharge pipe connected to the pressure relief devices
(Expansion Valve and Temperature / Pressure Relief Valve) must be installed in a continuously
downward direction and in a frost free environment.
The water may drip from the discharge pipe of the pressure relief device and that this pipe must
be left open to the atmosphere. The pressure relief device is to be operated regularly to remove
lime deposits and to verify that it is not blocked.
G3 Requirement
“...there shall be precautions...to ensure that the hot water discharged from safety devices is
safely conveyed to where it is visible but will not cause danger to persons in or about the building”.
Worked example of discharge pipe sizing (Taken from Building Regulations 2000, G3,
2010 edition)
The example below is for a G1” temperature relief valve with a discharge pipe (D2) having 4 No.
elbows and length of 7m from the tundish to the point of discharge.
From Table 5:
Maximum resistance allowed for a straight length of 35mm copper discharge pipe (D2) from a
G1” temperature relief valve is 9m.
Subtract the resistance for 4 No. 35mm elbows at 1.4m each = 5.6m
Therefore the permitted length equates to: 3.4m
3.4m is less than the actual length of 7m therefore calculate the next largest size.
Maximum resistance allowed for a straight length of 42mm pipe (D2) from a G1” temperature
relief valve equates to 18m.
Subtract the resistance of 4 No. 42mm elbows at 1.7m each = 6.8m
Therefore the maximum permitted length equates to: 11.2m
As the actual length is 7m, a 42mm (D2) copper pipe will be satisfactory.
Warnings
1. Under no circumstances should the factory tted Temperature /Pressure Relief Valve be
removed other than by authorised Heatrae Sadia personnel. To do so will invalidate any
guarantee or claim.
2. The Cold Water Combination Valve must be tted to the mains water supply to the Remeha
Flexistor unit.
3. No control or safety valves should be tampered with or used for any other purposes.
4. Water may drip from the discharge pipe of the pressure relief device (Expansion Valve) and
this pipe must be left open to atmosphere. The discharge pipe should not be blocked or used
for any other purpose.
5. The tundish must be installed so that it is visible to the end user.
6. The tundish and drain valve must be installed away from any electrical components.
7. No valve should be tted between the 8 bar or 13 bar pressure relief valve and the Remeha
Flexistor unit.
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Flexistor at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Flexistor in the language / languages: English as an attachment in your email.

The manual is 2.7 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info