The following extract is taken from latest G3 Regulations
Discharge pipes from safety devices
Discharge pipe D1
3.50 Safety devices such as temperature relief valves or combined temperature and pres-
sure relief valves (see paragraphs 3.13 or 3.18) should discharge either directly or by way of a
manifold via a short length of metal pipe (D1) to a tundish.
3.51 The diameter of discharge pipe (D1) should be not less than the nominal outlet size of the
safety device, e.g. temperature relief valve.
3.52 Where a manifold is used it should be sized to accept and discharge the total discharge from
the discharge pipes connected to it.
3.53 Where valves other than a temperature and pressure relief valve from a single unvented
hot water system discharge by way of the same manifold that is used by the safety devices, the
manifold should be factory tted as part of the hot water storage system unit or package.
Tundish
3.54 The tundish should be vertical, located in the same space as the unvented hot water stor-
age system and be tted as close as possible to, and lower than, the safety device, with no more
than 600mm of pipe between the valve outlet and the tundish (see Diagram 1).
Note: To comply with the Water Supply (Water Fittings) Regulations, the tundish should incorpo-
rate a suitable air gap.
3.55 Any discharge should be visible at the tundish. In addition, where discharges from safety
devices may not be apparent, e.g. in dwellings occupied by people with impaired vision or mo-
bility, consideration should be given to the installation of a suitable safety device to warn when
discharge takes place, e.g. electronically operated.
Discharge pipe D2
3.56 The discharge pipe (D2) from the tundish should:
a. have a vertical section of pipe at least 300mm long below the tundish before any elbows or
bends in the pipework (see Diagram 1); and
b. be installed with a continuous fall of at least 1 in 200 thereafter.
3.57 The discharge pipe (D2) should be made of:
a. metal; or
b. other material that has been demonstrated to be capable of safely withstanding temperatures
of the water discharged and is clearly and permanently marked to identify the product and per-
formance standard (e.g. as specied in the relevant part of BS 7291- 1:2006 Thermostatic pipes
and ttings for hot and cold water for domestic purposes and heating installations in buildings.
General requirements).
3.58 The discharge pipe D2 should be at least one pipe size larger than the nominal outlet size
of the safety device unless its total equivalent hydraulic resistance exceeds that of a straight pipe
9m long, i.e. for discharge pipes between 9m and 18m the equivalent resistance length should
be at least two sizes larger than the nominal outlet size of the safety device; between 18 and
27m at least 3 sizes larger, and so on; bends must be taken into account in calculating the ow
resistance. See Diagram 1, Table 3.1 and the worked example.
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Flexistor at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Flexistor in the language / languages: English as an attachment in your email.

The manual is 2.7 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info