6 | Installation and electrical connection
14 / 34 5111967B_OI-II_Webasto Unite_EN
Fig.36
The power optimizer meter must be installed just after the
mains switch of the house, as shown in the illustration above.
1. Install the power optimizer meter
2. Install the wiring according to the figure and table below.
7
Fig.37
Terminal Description
5 (CN20-1) B (COM)
6 (CN20-2) A (COM)
6.8 Using the Mode selection switch
The Webasto Unite has the following modes:
lOperation Mode 1 (Standard Charging): This mode is the
factory default setting.
lOperation Mode 2 No function
lOperation Mode 3 No function
1
2
3
Fig.38
lThe mode selection switch must be in position 1.
6.9 Setting up Load shedding /
Potential-free contact
The Webasto Unite supports load shedding. Load shedding
provides immediate charging-current reduction in case of lim-
ited supply. Load shedding can be used in any mode, including
Standalone and OCPP-connected modes. The load-shedding
triggering signal is a dry contact, (potential free) signal. This sig-
nal must be provided externally, and must be connected to ter-
minals 3 and 4 on the power board.
lWhen load shedding is activated by closing the contacts
with an external device (such as ripple control receivers),
then the charging current is reduced to 8 A.
lWhen load shedding is deactivated by opening the con-
tacts, then the charging process continues at the maximum
available current.
lIn a normal state, when there is no signal connected to the
load shedding input (contacts open between terminal 3
and 4), the charging station supplies the maximum avail-
able current.
Fig.39
Terminal Input
3 Load Shedding Input +
4 Load Shedding Input -
Load Shedding
Input State
Behaviour
Open Contact Charge with maximum available current.
Closed Contact Charge with 8 A.
lConnect the potential free contact load-shedding signal.
6.10 Monitoring welded relay contact
failures
In accordance with IEC 61851-1 and EV/ZE Ready requirements,
the Webasto Unite has a welded contactor sensing function. If a
welded contact occurs, then the main board provides a shunt
trip 230 V signal. Note that the CN33 connector output termin-
als must be used to detect welded contact failure for the relays.
In case of a welded contact for the relays, the CN33 connector
output will be 230 V AC. The output which has 230V AC must
be connected to a shunt trip for RCCB triggering as shown be-
low.
1
2
EVSE
N
L1_W
CN33
230V
SHUNT
TRIP
RCBB
or
MCB
Fig.40
The cabling must be done as shown below. The connector
(CN33) terminals must be connected to a shunt trip module.
The shunt Trip module is mechanically coupled to an RCCB (or
MCB) at the fuse box of the charging station.
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for NewMotion Home Advanced 2.1 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of NewMotion Home Advanced 2.1 in the language / languages: English, German, Dutch, French as an attachment in your email.

The manual is 4.78 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info