Above a Fireplace
In this type of installation, the chimney connector rises
from the stove, turns 90°, and then goes into the fireplace
chimney (Fig. B) The liner of the fireplace chimney should
extend at least to the point at which the chimney connector
enters the chimney. Follow all the guidelines for installing
a chimney connector into a freestanding masonry chimney,
and pay special attention to these additional points:
• Double check the connector clearance from the
ceiling: 18” minimum.
• The fireplace damper must be closed and sealed
to prevent room air from being drawn up the flue,
thereby reducing the draft. However, it must
be possible to re-open the damper in order to
inspect the chimney.
Fig. B: Chimney connector enters the chimney above a fireplace
Wall Pass-Through
Whenever possible, design your installation so that the wall connector does not pass through a combustible wall. If
you are considering a wall pass-through in your installation, check with your building inspector before you begin. Also
check with the chimney connector manufacturer for any specific requirements. Accessories are available for use as
wall pass-throughs. If using one of these, make sure it has been tested and listed for use as a wall pass-through.
Fig. C: An example of an approved wall pass-through
9
Chimney connection is a freestanding
Chimney connector enters chimney above the
An approved wall pass-through for the United States
Wall Stud
The National Fire Protection Association (NFPA) has
established guidelines for passing chimney connectors
through combustible walls. Many building code
inspectors follow these guidelines when approving
installations.
The methods approved by the NFPA are:
Cutting away all combustible material in the
wall a sufficient distance from the single wall connector,
to provide the required 12” (300 mm) clearance for the
connector. Any material used to close the opening must
be non-combustible (as in Fig . C).
Using a section of double-wall chimney with a
9” (230 mm) clearance to combustibles.
Placing a chimney connector pipe inside
a ventilated thimble, which is then separated from
combustibles by 6” (150 mm) of fibreglass insulating
material.
• Placing a chimney connector pipe inside a section
of 9” (230 mm) diameter, solid-insulated factory built
chimney, with two inches of air space between the
chimney section and the combustibles.
Chimney Connector
Floor Protection
minimum 18”
seal the damper
9


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Nestor Martin S33 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Nestor Martin S33 in the language / languages: English as an attachment in your email.

The manual is 2,25 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Nestor Martin S33

Nestor Martin S33 User Manual - English - 48 pages

Nestor Martin S33 User Manual - Dutch, French - 25 pages

Nestor Martin S33 User Manual - Spanish - 48 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info