Standard Installation Procedure
1. Position the unit no closer than the minimum clearances to combustible materials. Check that no overhead
cross members in the ceiling or roof will be cut. Reposition unit if necessary, being careful not to move closer
than the minimum clearances.
2. Mark the position of the required floor protector on the floor. Remove the unit and install the floor protector.
3. Position the unit on the floor protector at the proper clearances.
4. Install a 6-inch diameter, minimum 24 MSG black or 26 MSG blued steel connector pipe on the flue collar of
the unit.
5. The stove is NOT to be connected to any air distribution duct or system. A chimney connector shall not
pass through an attic or roof space, closet or similar concealed space, or a floor, or ceiling. Where passage
through a wall or partition of combustible construction is desired, the installation shall conform to CAN/CSA-
B365, Installation Code for Solid-Fuel-Burning Appliances and Equipment. (Canadian installations only).
6. Use a 6” chimney connector adapter to connect the chimney connector up to the chimney. The small ends of
the chimney connector should all point down to ensure a drip-free installation.
7. Check that all clearances are still within the allowable tolerances.
8. Secure adjoining sections of chimney connector to each other using three equally spaced sheet metal screws.
Secure the connector pipe to flue collar using three equally spaced sheet metal screws. DO NOT secure
chimney connector to chimney with screws.
9. The unit must be connected to either:
• a code-approved masonry chimney with a flue liner, or
• a 6 inch diameter factory built chimney complying with the requirements for Type HT chimneys in the
standard UL 103 and ULC S629.
WARNING:
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
UNIT MUST BE INSTALLED ACCORDING TO ALL LOCAL CODES. A BUILDING PERMIT MUST BE OBTAINED
BEFORE INSTALLING.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE.
DO NOT INSTALL IN A MOBILE HOME.
READ ALL INSTRUCTIONS CAREFULLY BEFORE STARTING THE INSTALLATION.
UNIT MUST BE PROPERLY INSTALLED OR LISTING WILL BE VOID.
INSTALLATIONS OTHER THAN THOSE SPECIFICALLY COVERED HEREIN HAVE NOT BEEN CONFIRMED BY
TEST AND ARE NOT COVERED BY THE LISTING.
Freestanding Installations
If the chimney connector must pass through a combustible wall to reach the chimney, follow the recommendations in
the Wall Pass-Through section that follows.
The opening through the chimney wall to the flue (the “breach”) must be lined with either a ceramic or metal cylinder,
called a “thimble”, which is securely cemented in place.
Fig. A: Chimney connection in a freestanding installation
8
Most chimney breeches incorporate thimbles, but the fit must
be snug and the joint between the thimble and the wall must be
cemented firmly (Fig. A)
A special piece called the “thimble sleeve”, slightly smaller in
diameter than standard connectors and most thimbles, will
facilitate the removal of the chimney connector system for
inspection and cleaning. Thimble sleeves are available from
your local dealer.
To install a thimble sleeve, slide it into the breech until it is flush
with the inner flue wall. Do not extend it into the actual flue
passage, as it could interfere with the draft.
The thimble sleeve should protrude 1-2” (25-50 mm) into the
room. User fire cement and thin gasketing to seal the sleeve
in place in the thimble. Secure the chimney connector to the
outer end of the sleeve with sheet metal screws.
Chimney
Elbow
Slip Pipe
Standard
Connector
Flue Liner
Flue Liner
Thimble
Flue Collar
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Nestor Martin S33 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Nestor Martin S33 in the language / languages: English as an attachment in your email.

The manual is 2,25 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Nestor Martin S33

Nestor Martin S33 User Manual - English - 48 pages

Nestor Martin S33 User Manual - Dutch, French - 25 pages

Nestor Martin S33 User Manual - Spanish - 48 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info