Installation
31
Climate 5000 MS – 6721830160 (2020/12)
3.3.4 Installing the outdoor unit
Place the box so it is facing upwards.
Cut and remove the packing straps.
Pull the box up and off and remove the packaging.
Prepare and install a floor or wall mounting bracket, depending on the
type of installation.
Set up or hang the outdoor unit.
When installing on the floor or wall mounting bracket, attach the
supplied drainage elbow and gasket (Fig. 7).
Remove the cover for the pipe connections (Fig. 9).
Establish pipe connections as described in Chapter 3.5.1.
3.4 Installing the air duct in built-in ducted indoor units
3.4.1 Installation of pipes and accessories
The appliance must be hung in order to install the pipes, etc.
If an air filter is not used, dust particles may accumulate in the heat
exchanger and cause malfunctions and leaks.
Cut the air filter (not included in scope of delivery) to the size of the
air inlet and attach.
To prevent the air discharged by the air conditioner from being drawn
back in directly, or to prevent a short circuit: plan the air outlet and air
inlet so that they are not too close to one another.
Before installing the air duct, make sure the static pressure of the air
duct is within the permitted range:
Table 13 External static pressure
Always incorporate isolators when connecting the air conduits to the
appliance in order to prevent the noise from the indoor unit being
transmitted to the ventilation pipes.
Attach the air duct as shown in Fig. 41.
Key to Fig. 41:
[1] Heat insulation layer
[2] Isolator
[3] Return air inlet
[4] For Inspection
[5] Built-in ducted indoor unit
[6] Air Outlet
Also insulate the pipes to prevent condensation.
3.4.2 Adjusting air inlet direction
(from the rear to the underside)
Carry out modification as shown in Fig. 42:
Remove filter grille [3].
Remove fan plate [1] and air inlet flange [2].
Bend fan plate on the rear through 90°.
Reinstall the fan plate in the position previously occupied by the air
inlet flange and vice-versa.
Guide the filter grille [3] into the air inlet flange.
3.4.3 Installing the fresh air duct
There is a fresh air intake opening on the built-in ducted indoor unit side
which can be used if required (Fig. 39).
No more than 15 % of the air volumetric flow rate can be introduced via
the fresh air intake opening.
3.5 Pipework connection
3.5.1 Connecting refrigerant pipes to the indoor and outdoor
unit
CAUTION
Discharge of refrigerant due to leaky connections
Refrigerant may be discharged if pipe connections are incorrectly
installed.
When reusing flared joints, always fabricate the flared part again.
Copper pipes are available in metric and imperial sizes, the flare nut
thread is however the same. The flared fittings on the indoor and outdoor
unit are intended for imperial sizes.
When using metric copper pipes, replace the flare nuts with nuts of a
suitable diameter ( Tab. 14).
Determine pipe diameter and length ( Page 28).
Cut the pipe to length using a pipe cutter ( Fig. 8).
Deburr the inside of the pipe at both ends and tap to remove swarf.
Insert the nut onto the pipe.
Widen the pipe using a flaring tool to the size indicated in the tab. 14.
It must be possible to slide the nut up to the edge but not beyond it.
Connect the pipe and tighten the screw fitting to the torque specified
in the tab. 14.
A connection pair (gas side and liquid side) exists for every indoor unit.
Different connection pairs must not be mixed ( Fig. 6).
Repeat the above steps for the other pipes.
NOTICE
Reduced efficiency due to heat transfer between refrigerant pipes
Thermally insulate the refrigerant pipes separately.
Fit the insulation on the pipes and secure.
Model External static pressure (Pa)
Pressure range Design pressure
CL5000MS 07 DCT
CL5000MS 09 DCT
0-40 25
CL5000MS 12 DCT 0-60 25
CL5000MS 18 DCT 0-100 25
31


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Nefit-Bosch Climate 5000 Multi Split at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Nefit-Bosch Climate 5000 Multi Split in the language / languages: English, German, Dutch, Danish, French, Italian, Polish, Portuguese, Turkish, Spanish as an attachment in your email.

The manual is 24.27 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Nefit-Bosch Climate 5000 Multi Split

Nefit-Bosch Climate 5000 Multi Split User Manual - English, German, Dutch, Danish, French, Italian, Polish, Portuguese, Turkish, Spanish - 64 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info