Installation
29
Climate 5000 MS – 6721830160 (2020/12)
Observe the maximum number of connected indoor units which
depends on the appliance type of the outdoor unit.
Observe maximum piping length and maximum difference in height
between the indoor units and outdoor unit.
Table 7 Piping lengths
Comply with maximum difference in height between the indoor units
and outdoor unit ( Fig. 5).
Observe pipe diameter and further specifications.
Table 8 Alternative pipe diameter
Table 9
3 Installation
3.1 Before installation
CAUTION
Risk of injury from sharp edges!
Wear protective gloves during installation.
CAUTION
Danger of burns!
During operation the pipes become hot.
Make sure, that the pipes cooled down before touching them.
Check the scope of delivery for damage.
Check whether a hissing sound due to negative pressure can be
detected when opening the pipes of the indoor unit.
3.2 Requirements for installation site
Observe minimum clearances (Chapter 2.5 on page 28).
Observe minimum room area.
Table 10 Minimum room area (1 of 3)
Table 11 Minimum room area (2 of 3)
Table 12 Minimum room area (3 of 3)
General notices regarding indoor units
Do not install the indoor unit in a room in which open ignition sources
(for example: open flames, an operating wall mounted gas boiler or
an operating electric heating system) are in operation.
The installation site must not be higher than 2000 m above sea level.
Keep the air inlet and air outlet clear of any obstacles to allow the air
to circulate freely. Otherwise poor performance and higher noise
levels may occur.
Keep TV, radio and and similar appliances at least 1 m away from the
unit and the remote control.
Do not install the indoor unit in rooms with a high humidity
(e.g. bathrooms or utility rooms).
Indoor units with a cooling capacity of 2.0 to 5.3 kW are designed for
a single room.
Notices regarding wall-mounted indoor units
The unit can be installed in a room with a floor area of 4 m2, if the
installation height is at least 1.8 m. If the installation height is lower,
the floor area must be accordingly larger.
Mount the indoor unit on a wall that absorbs vibrations.
Notices regarding ceiling-mounted indoor units
The ceiling construction and suspension system (on site) must be
able to support the weight of the appliance.
Unit type
Climate 5000 MS ...
Maximum overall
pipe length1) [m]
1) Gas side or liquid side
Maximum pipe
length per
connection1) [m]
14 OUE 40 25
18 OUE
21 OUE 60 30
27 OUE
28 OUE 80 35
36 OUE
42 OUE 80 35
Pipe diameter [mm] Alternative pipe diameter [mm]
6.35 (1/4") 6
9.53 (3/8") 10
12.7 (1/2") 12
Specification of the pipes
Min. piping length 3 m
Standard piping length 7.5 m
Additional refrigerant if the pipe length
exceeds 7.5 m (liquid side)
With Ø 6.35 mm (1/4"):
12 g/m
With Ø 9.53 mm (3/8"):
24 g/m
Piping Thickness With Ø 9.53 mm (3/8''):
≥ 0.8 mm.
With Ø 15.9 mm (5/8''):
≥ 1.0 mm *******
Thickness of insulation against heat 6 mm
Material of insulation against heat Polyethylene foam
Installation
height [m]
Additional refrigerant [kg]
1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7
Minimum room area [m2]
0.6 9.0 10.5 12.5 14.5 17.0 19.5 22.0 25.0
1.8 1.0 1.5 1.5 2.0 2.0 2.5 2.5 3.0
2.2 1.0 1.0 1.0 1.5 1.5 1.5 2.0 2.0
Installation
height [m]
Additional refrigerant [kg]
1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5
Minimum room area [m2]
0.6 28.0 31.0 34.5 38.0 41.5 45.5 49.5 54.0
1.8 3.5 3.5 4.0 4.5 5.0 5.0 5.5 6.0
2.2 2.5 2.5 3.0 3.0 3.5 3.5 4.0 4.0
Installation
height [m]
Additional refrigerant [kg]
2.6 2.7 2.8
Minimum room area [m2]
0.6 58.0 63.0 67.5
1.8 6.5 7.0 7.5
2.2 4.5 5.0 5.0
29


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Nefit-Bosch Climate 5000 Multi Split at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Nefit-Bosch Climate 5000 Multi Split in the language / languages: English, German, Dutch, Danish, French, Italian, Polish, Portuguese, Turkish, Spanish as an attachment in your email.

The manual is 24.27 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Nefit-Bosch Climate 5000 Multi Split

Nefit-Bosch Climate 5000 Multi Split User Manual - English, German, Dutch, Danish, French, Italian, Polish, Portuguese, Turkish, Spanish - 64 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info