Installation
Climate 5000 MS – 6721830160 (2020/12)
30
Notices regarding outdoor units
The outdoor unit must not be exposed to machine oil vapour, hot
spring vapour, sulphur gas, etc.
Do not install the outdoor unit directly next to water or where it is
exposed to sea air.
The outdoor unit must always be kept free of snow.
There must be no disruption caused by extract air or operating noise.
Air should be able to circulate freely around the outdoor unit, but the
appliance must not be exposed to strong wind.
Condensate that forms during operation must be able to drain off
easily. Lay a drain hose if required. In cold regions, installation of a
drain hose is not advisable as it could freeze.
Place the outdoor unit on a stable base.
3.3 Unit installation
NOTICE
Incorrect assembly can cause material damage.
If the unit is assembled incorrectly, it may fall off the wall.
Only install the unit on a solid flat wall. The wall must be capable of
supporting the weight of the unit.
Only use screws and rawl plugs that are suitable for the wall type and
weight of the unit.
3.3.1 Installing the indoor unit on the wall
Open the box at the top and lift the indoor unit out and up.
Place the indoor unit with the moulded parts of the packaging face
down (Fig. 15).
Undo screw and remove the mounting plate on the rear of the indoor
unit.
Determine the installation site, taking the minimum clearances into
consideration (Fig. 14).
Attach the mounting plate with a screw and wall plug centrally and at
the top of the wall and level out (Fig. 16).
Fasten the mounting plate with a further four screws and wall plugs so
that the mounting plate lies flat on the wall.
Drill wall outlet for the piping (wall outlet should be behind the indoor
unit as a recommendation Fig. 17).
Change the position of the condensate pipe if necessary
(Fig. 19).
The pipe fittings on the indoor unit are generally located behind the
indoor unit. We recommend extending the pipes before mounting the
indoor unit.
Establish pipe connections as described in Chapter 3.5.1.
Bend the piping in the required direction if necessary, and knock out
an opening on the side of the indoor unit (Fig. 21).
Route the piping through the wall and attach the indoor unit to the
mounting plate (Fig. 22).
Fold up the top cover and remove one of the two filter elements
(Fig. 23).
Insert the cold catalyst filter which is included in the scope of delivery
into the filter element, and mount the filter element again.
If it is necessary to take the indoor unit off the mounting plate:
Pull the underside of the casing down in the area of the two recesses
and pull the indoor unit forwards (Fig. 24).
3.3.2 Installing the indoor unit in the ceiling
We recommend preparing the pipes before hanging the indoor unit so
that only the pipes need to be connected.
Open the box at the top and lift the indoor unit out and up.
Determine the installation site, taking the minimum clearances and
orientation of the pipes into consideration:
Cassette indoor units: Fig. 31 to 29
Built-in ducted indoor units: Fig. 39 to 40
Make sure that the appliance fits between the structural ceiling and drop
ceiling.
In the case of the cassette indoor unit, the fascia must be flush with
the drop ceiling.
The clearance between the built-in ducted indoor unit and drop
ceiling must be at least 24 mm.
Define and mark the position of the suspension bolts on the ceiling.
DANGER
Risk of injury!
The ceiling attachment must be suitable for carrying the weight of the
indoor unit. We recommend using M10 threaded rods in order to be able
to adjust the height precisely. Suitable nuts and washers are included in
the scope of delivery of the indoor unit.
DANGER
Risk of injury!
At least two persons are required to hang the unit and fasten it securely.
Do not install the unit on your own.
Hang the unit on the suspension bolts with the washers and nuts
included in the scope of delivery.
Position the indoor unit at the correct height and align horizontally by
turning the nuts on the threaded rods.
NOTICE
If the unit is not level condensate may leak out.
Use a spirit level to align the unit horizontally.
Secure the unit at the correct installation position with lock nuts.
Establish pipe connections as described in Chapter 3.5.1.
3.3.3 Installing the cover for cassette indoor units
Remove the air inlet grille from the cover (Fig. 32).
Attach cover to the indoor unit with screws provided, paying
attention to orientation (Fig. 33).
The cover must rest evenly and tightly against the indoor unit.
Only reinstall the air inlet grille when establishing the electrical
connection.
30


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Nefit-Bosch Climate 5000 Multi Split at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Nefit-Bosch Climate 5000 Multi Split in the language / languages: English, German, Dutch, Danish, French, Italian, Polish, Portuguese, Turkish, Spanish as an attachment in your email.

The manual is 24.27 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Nefit-Bosch Climate 5000 Multi Split

Nefit-Bosch Climate 5000 Multi Split User Manual - English, German, Dutch, Danish, French, Italian, Polish, Portuguese, Turkish, Spanish - 64 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info