- The sensor unit is not exposed to direct draughts. When used in freezer rooms, the sensor unit must first be acclimatised to the ambient temperature.
- The sensor unit reaches the deepest point in the monitoring area
- It is approx. 30 cm away from the floor
- The sensor unit can be installed on a vertical wall
- The sensor unit is protected from mechanical impacts as far as possible
Drill two holes at a distance of 40 mm with an 8 mm drill and insert the dowels (1). Use the screws (3) to screw the DIN rail (2) to the wall and tighten the screws.
Position the lower part of the sensor unit (4) housing onto the rail from above, and press the sensor unit downward until the clamping mechanism snaps in with
an audible click. The sensor unit can be removed again from the DIN rail by pulling the terminal snap-in mechanism.. Secure the control cable to the sensor unit
using the plug (5). Tighten the union nut on the plug.
A maintenance plate is mounted on the sensor unit. Mark this with the next replacement date with a ballpoint pen or screwdriver. This should be replaced every
4 years of operation.
CO2 sensor unit installation
2.4Installing the CO2 warning unit (PA)
As a precondition for installation, a qualified electrician must first of all install a power distributor or socket at ceiling height in the entrance area.
The warning unit is fitted with a 2.5 m long power cable and plug. The warning unit can be connected to the mains power either permanently, or via a plug. You
must make sure that a continuous power supply can be ensured.
The PA warning unit can only be permanently connected to a 230 V / 50 Hz power supply and comes with a plug for the necessary "one-man initialisation".
A permanent installation may only be performed by a qualified technician (electrician)!
The warning unit must be installed immediately in front of the danger area!
Disconnect the PA warning unit during initialisation and
Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.
Product:
Forumrules
To achieve meaningful questions, we apply the following rules:
First, read the manual;
Check if your question has been asked previously;
Try to ask your question as clearly as possible;
Did you already try to solve the problem? Please mention this;
Is your problem solved by a visitor then let him/her know in this forum;
To give a response to a question or answer, do not use this form but click on the button 'reply to this question';
Your question will be posted here and emailed to our subscribers. Therefore, avoid filling in personal details.
Register
Register getting emails for Kundo xT CO2 Control at:
new questions and answers
new manuals
You will receive an email to register for one or both of the options.
Get your user manual by e-mail
Enter your email address to receive the manual of Kundo xT CO2 Control in the language / languages: English as an attachment in your email.
The manual is 1,55 mb in size.
You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.
If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.
The email address you have provided is not correct.
Please check the email address and correct it.
Your question is posted on this page
Would you like to receive an email when new answers and questions are posted? Please enter your email address.