When a safety device is activated, an error code will be displayed on the user interface.
A list of all errors and corrective actions can be found in the table below.
Reset the safety by turning the unit OFF and back ON.
In case this procedure for resetting the safety is not successful, contact your local dealer.
13.4 Error codes
The power consumption parameter is preparatory. some parameter is not be activated in the system, the parameter will
show "--"
The heat pump capacity is for reference only, not used to judge the ability of the unit. The accuracy of sensor is ±1
.
The flow rates parameters are calculated according to the pump running parameters,the deviation is different at different flow
rates,the maximum of deviation is 25%.
NOTE
OPERATION PARAMETER
#01
IDU TARGET FREQUENCY 46Hz
ADDRESS
FREQUENCY LIMITED TYPE 5
FAN SPEED 600R/MIN
SUPPLY VOLTAGE 230V
DC GENERATRIX VOLTAGE 420V
DC GENERATRIX CURRENT 18A
7/9
OPERATION PARAMETER
#01
TW_I PLATE W-INLET TEMP. 30°C
ADDRESS
T2 PLATE F-OUT TEMP. 35°C
TW_O PLATE W-OUTLET TEMP. 35°C
T2B PLATE F-IN TEMP. 35°C
Th COMP. SUCTION TEMP. 5°C
Th COMP. DISCHARGE TEMP. 75°C
8/9
OPERATION PARAMETER
#01
T4 OUTDOOR AIR TEMP. 5°C
ADDRESS
TF MODULE TEMP. 55°C
T3 OUTDOOR EXCHARGE TEMP. 5°C
P1 COMP. PRESSURE 2300kPa
ODU SOFTWARE 01-09-2018V01
HMI SOFTWARE 01-09-2018V01
9/9
ERROR
CODE
MALFUNCTION
OR PROTECTION
FAILURE CAUSE
AND CORRECTIVE ACTION
Water flow fault (E8
displayed 3 times)
1.The wire circuit is short connected or open. Reconnect the wire
correctly.
2.Water flow rate is too low.
3. Water flow switch is failed, switch is open or close continuously,
change the water flow switch.
Phase loss or neutral wire and
live wire are connected
reversely
1.Check the power supply cables should be connected stable, to avoid
phase loss.
2.Check the power supply cables sequence, change any two cables
sequence of the three power supply cables.
Communication fault between
controller and main control
board of hydraulic module
1.The wire doesn’t connect between wired controller and unit. connect
the wire.
2.Communication wire sequence is not right. Reconnect the wire in
the right sequence.
3. Whether there is a high magnetic field or high power interfere, such
as lifts, large power transformers, etc..
4. To add a barrier to protect the unit or to move the unit to the other
place.
Final outlet water temp. sensor
(T1) fault.
1. Check the resistance of the sensor
2. The T1 sensor connector is loosen. Reconnect it.
3.The T1 sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive.
4.The T1 sensor failure, change a new sensor.
Water tank temp. sensor
(T5) fault.
1. Check the resistance of the sensor
2.The T5 sensor connector is loosen. Reconnect it.
3.The T5 sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
4.The T5 sensor failure, change a new sensor
65


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Kaysun Aquantia PRO Monobloc - KHP-MO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Kaysun Aquantia PRO Monobloc - KHP-MO in the language / languages: English as an attachment in your email.

The manual is 27.62 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Kaysun Aquantia PRO Monobloc - KHP-MO

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - German - 88 pages

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - Dutch - 88 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info