ERROR
CODE
MALFUNCTION
OR PROTECTION
FAILURE CAUSE
AND CORRECTIVE ACTION
The condenser outlet
refrigerant temperature sensor
(T3) fault.
1. Check the resistance of the sensor
2. The T3 sensor connector is loosen. Reconnect it.
3.The T3 sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
4. The T3 sensor failure, change a new sensor.
The ambient temperature
sensor (T4) fault.
1. Check the resistance of the sensor
2. The T4 sensor connector is loosen. Reconnect it.
3.The T4 sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
4. The T4 sensor failure, change a new sensor.
The balance tank up temp.
sensor (Tbt1) fault.
1.Check the resistance of the sensor.
2.The Tbt1 sensor connector is loosen,reconnect it.
3.The Tbt1 sensor connector is wet or there is water in,remove the
water ,make the connector dry.Add waterproof adhesive.
4.The Tbt1 sensor failure,change a new sensor.
Water flow fault.
Check that all shut off valves of the water circuit are completely open.
1.Check if the water filter needs cleaning.
2.Refer to "9.4 Charging water"
3.Make sure there is no air in the system(purge air).
4. Check on the manometer that there is sufficient water pressure. The
water pressure must be >1 bar.
5.Check that the pump speed setting is on the highest speed.
6.Make sure that the expansion vessel is not broken.
7. Check that the resistance in the water circuit is not too high for the
pump (refer to "Setting the pump speed" ).
8. If this error occurs at defrost operation (during space heating or
domestic water heating), make sure that the backup heater power
supply is wired correctly and that fuses are not blown.
9.Check that the pump fuse and PCB fuse are not blown.
Compressor suction temp.
sensor (Th) fault.
1.Check the resistance of the sensor.
2. The Th sensor connector is loosen. Reconnect it.
3.The Th sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
4. The Th sensor failure, change a new sensor.
Compressor discharge temp.
sensor (Tp) fault.
1.Check the resistance of the sensor.
2. The Tp sensor connector is loosen. Reconnect it.
3.The Tp sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
4. The Tp sensor failure, change a new sensor.
Solar panel temp.sensor
(Tsolar) fault.
1.Check the resistance of the sensor.
2.The Tsolar sensor connector is loosen,reconnect it.
3.The Tsolar sensor connector is wet or there is water in,remove the
water ,make the connector dry.Add waterproof adhesive.
4.The Tsolar sensor failure,change a new sensor.
66


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Kaysun Aquantia PRO Monobloc - KHP-MO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Kaysun Aquantia PRO Monobloc - KHP-MO in the language / languages: English as an attachment in your email.

The manual is 27.62 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Kaysun Aquantia PRO Monobloc - KHP-MO

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - German - 88 pages

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - Dutch - 88 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info