Symptom 3: Pump is making noise (cavitation)
POSSIBLE CAUSES CORRECTIVE ACTION
There is air in the system. Purge air.
Water pressure at pump
inlet is too low.
• Check on the manometer that there is sufficient water pressure.
The water pressure must be > 1 bar (water is cold).
• Check that the manometer is not broken.
• Check that the expansion vessel is not broken.
• Check that the setting of the pre- pressure of the expansion
vessel is correct (refer to "9.3 water piping/Checking the
water volume and expansion vessel pre-pressure").
Symptom 4: The water pressure relief valve opens
POSSIBLE CAUSES CORRECTIVE ACTION
The expansion vessel isbroken. Replace the expansion vessel.
The filling water pressure
in the installation is
higher than 0.3MPa.
Make sure that the filling water pressure in the installation is about
0.15~0.20MPa (refer to "9.3 water piping/Checking the water volume and
expansion vessel pre-pressure").
Symptom 6: Space heating capacity shortage at low outdoor temperatures
Symptom 5: The water pressure relief valve leaks
POSSIBLE CAUSES CORRECTIVE ACTION
Dirt is blocking the water
pressure relief valve
outlet.
Check for correct operation of the pressure relief valve by turning the red
knob on the valve counter clockwise:
• If you do not hear a clacking sound, contact your local dealer.
• In case the water keeps running out of the unit, close both the
water inlet and outlet shut-off valves first and then contact your
local dealer.
POSSIBLE CAUSES CORRECTIVE ACTION
Backup heater operation
is not activated.
Too much heat pump
capacity is used for
heating domestic hot
water (applies only to
installations with a
domestic hot water tank).
Check that the “t_DHWHP_MAX” and “t_DHWHP_RESTRICT” are
configured appropriately:
• Make sure that the “DHW PRIORITY” in the user interface is
disabled.
• Enable the “T4_TBH_ON” in the user interface/FOR SERVICEMAN
to activate the booster heater for domestic water heating.
Check that the "OTHER HEATING SOURCE/ BACKUP HEATER"is
enabled, see "10.7 Field settings" Check whether or not the thermal
protector of the backup heater has been activated (refer to “Controls parts
for backup heater(IBH) ” ). Check if booster heater is running, the backup
heater and booster heater can’t operate simultaneously.
Symptom 7: Heat mode can’t change to DHW mode immediately
POSSIBLE CAUSES CORRECTIVE ACTION
Volume of tank is too
small and the location of
water temperature probe
not high enough
• Set “dT1S5” to 20
°C
, and set “t_DHWHP_RESTRICT” to minimum value.
• Set dT1SH to 2
°C
.
• Enable TBH, and TBH should be controled by the outdoor unit.
• If AHS(boiler) is available, turn boiler on first, if requirement for
turn heat pump on is fullfilled, the heat pump will turn on.
• If both TBH and AHS are not available, try to change the postion
of T5 probe(refer to 2 General information/Domestic hot water
tank).
63


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Kaysun Aquantia PRO Monobloc - KHP-MO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Kaysun Aquantia PRO Monobloc - KHP-MO in the language / languages: English as an attachment in your email.

The manual is 27.62 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Kaysun Aquantia PRO Monobloc - KHP-MO

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - German - 88 pages

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - Dutch - 88 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info