Note on Adding Refrigerant
Some systems require additional charging depending on pipe lengths. The standard pipe length varies according to
local regulations. The standard pipe length is 5m (16'). The refrigerant should be charged from the service port on
the outdoor unit's low pressure valve. The additional refrigerant to be charged can be calculated using the following
formula:
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Connective Pipe
Length (m)
Air Purging
Method Additional Refrigerantl
≤ Standard pipe length Vacuum Pump N/A
< Standard pipe length Vacuum Pump
Liquid side: Ø 6,35 (Ø0,25")
R-32:
(Pipe length - standard length) x
12 g/m
Liquid side: Ø 9,52 (Ø0,375")
R-32:
(Pipe length - standard length) x
24g/m
CAUTION
DO NOT mix refrigerant types.
31


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Kaysun AKAY-CF 52 DR10 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Kaysun AKAY-CF 52 DR10 in the language / languages: English as an attachment in your email.

The manual is 3.88 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Kaysun AKAY-CF 52 DR10

Kaysun AKAY-CF 52 DR10 User Manual - German - 36 pages

Kaysun AKAY-CF 52 DR10 User Manual - Dutch - 36 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info