3.1 Installation and connection
Read these instructions before installing the char-
ging station carefully. Alfen ICU B.V. are not liable
for any consequential damages that occur due to
the use of this manual.
The installation must be performed by qualied
personnel that have read this manual and opera-
te in accordance with the guidelines IEC 60364.
Otherwise it may result in injury or dangerous si-
tuations when dealing with electricity.
NOTICE
Work may not be performed when it is raining or
the air humidity is higher than 95%.
NOTICE
A charging station should always be installed on
a dedicated circuit.
NOTICE
Danger to life through improper installation!
Non-observance of the following installation and
environmental requirements can lead to dange-
rous situations when dealing with electricity.
! DANGER!
The electrical system must be dead (disconnec-
ted from the power supply) during all installation
and maintenance work.
! DANGER!
3.2 Requirements for assembly and
installation
Cables should be laid based on maximum char-
ging rate of the charging station under conti-
nuous load (no diversity). The cable diameters
in this manual are indicative. The technician is
responsible for determining the correct cable dia-
meter and compliance with applicable standards.
NOTICE
Make sure that the following requirements for the
installation of the ICU Compact are fullled:
The cable route from the main distribution to the
ICU Compact must be secured with a miniature
circuit breaker (MCB) with characteristic B or a
screw or blade fuse gG against overvoltage and
short circuit
The cable route must be secured against acci-
dental contact 30 mA by a type A or B-residual-
current circuit breaker
The cable route and the charging station are
part of a TN-S system; the device is grounded
via the main distributor
The cable route must be laid in accordance with
applicable standards
The cable tray is made of copper cable with
a maximum conductor temperature of at least
90 °C
Installation requirements may be dependent on
the location.
NOTICE
3. Mounting and connecting
Type Protection Option 1 Protection Option 2 Min. core
cross section
1 x type 2 charging
socket, 1-phase, 16 A
1 x 20 A gG-fuses + 20 A - 30 mA
residual-current circuit breaker
20 B - 30 mA 1p + N
residual-current fuse
3 x 4 mm²
1 x type 2 charging
socket, 3-phase, 16 A
3 x 20 A gG-fuses + 20 A - 30 mA
residual-current circuit breaker
20 B - 30 mA 4p
residual-current fuse
5 x 4 mm²
1 x type 2 charging
socket, 3-phase, 32 A
3 x 35 A gG-fuses + 40 A - 30 mA
residual-current circuit breaker
40 B - 30 mA 4p
residual-current fuse
5 x 6 mm²
Mounting and connecting
The table below shows the safety options and the necessary cable diameters:
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for ICU Compact at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of ICU Compact in the language / languages: English as an attachment in your email.

The manual is 4,85 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of ICU Compact

ICU Compact User Manual - German - 18 pages

ICU Compact User Manual - Dutch - 8 pages

ICU Compact User Manual - French - 10 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info