Galaxy 2 Series Installation Manual
52 - Zones (cont’d)
09 Keyswitch
The Keyswitch function allows a zone to be used as an on/off switch for the system or assigned groups.
Operating a Keyswitch zone when the system is unset starts the timed full setting routine, therefore the exit
time is applicable. The system sets when the exit time expires or a Final or Push Set is activated.
If the system is set, operating a Keyswitch immediately unsets the assigned groups; there is no entry time
countdown.
The Keyswitch operation is as follows: 1k to 2k sets the system; 2k to 1k unsets the system.
NOTE: The activated zones are not displayed on the keypad when a Keyswitch is used to reset the alarm.
Keyswitch operation with groups enabled
When groups are enabled, a keyswitch zone will set and unset only the group that it is programmed to.
However, if the keyswitch is programmed to the common group (group four), then it will set and unset
the groups in the common group map (see Option 63.1.2).
13 PA
The PA (Personal Attack) function is continuously operational. Activation of this zone type overrides the Bell
Delay parameter and causes an instant full alarm condition that requires to be reset with an authorised user
code.
14 PA Silent
The PA Silent function is identical to the PA function, with the exception that there is no audible or visual
indication of the activation; that is, no bells or strobes are activated. Only the PA output (normally channel 2
on the digital communicator) signals the alarm. The activation (+) and restoral (–) of PA Silent zones is
recorded in the event log.
17 Link
This has no alarm function but can be used to activate links.
18 Spare
The Spare function allows any zones that are not being used to be ignored by the system; the resistance
readings from the circuit - including the tamper conditions - do not activate an alarm condition.
NOTE: It is recommended that all unused zones are programmed as Spare and that a 1k 1% resistor is
connected across each of these zones.
19 Fire
The Fire function is continuously operational. When activated, a FIRE zone overrides the Bell Delay pa-
rameter and activates an instant alarm (Bell, Strobe and Fire). The keypad buzzer and control panel horn
output, if fitted, emit an interrupted tone (one second on, 0.5 seconds OFF), easily distinguishable from all
other alarm conditions. Any valid code entry cancels the Fire activation.
85


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Honeywell Galaxy 2 Series at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Honeywell Galaxy 2 Series in the language / languages: English as an attachment in your email.

The manual is 1,28 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Honeywell Galaxy 2 Series

Honeywell Galaxy 2 Series User Manual - Dutch - 20 pages

Honeywell Galaxy 2 Series Usermanual and installation guide - Dutch - 148 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info