812035
6
Zoom out
Zoom in
Previous page
1/40
Next page
6
The following must be adhered to as
minimum distance from combustible or
temperature-sensitive materials (e.g.
furniture, wallpaper, wood paneling) or from
supporting walls respectively (see drawing):
A 5 cm to the rear wall,
B 10 cm to the side walls and
C 80 cm in the radiation range.
Picture 2: Safety distances
The chimney (chimney or flue) must be
designed e.g. from stainless steel or ceramic
(glazed inside), so that this cannot soot up.
This is necessary due to the low waste gas
temperature of your pellet stove.
For the connection to the flue, common
smoke tubes can be used. Approved flexible
steel tubes are also suitable.
Since, as a result of the method of operation
of the pellet stove with induced draught
ventilator, overpressure can develop at the
flue-gas outlet, all flue-gas lines up to the
chimney entry must be designed gas-tight. It
is also absolutely necessary to ensure, that
the smoke tube does not project into the free
cross-section of the chimney. For the
introduction into the chimney, the use of a
wall padding is recommended (see Picture 3).
For longer waste gas conduction, horizontal
sections and bottlenecks must be avoided
and special insulated smoke tubes should be
used; piping ascending towards the chimney
is recommended.
Picture 3: Chimney connection
1 = Wall padding
2 = Gas-tight piping
3 = Underlay plate
External air supply:
In air-tight buildings, during the operation of
the pellet stove a reduction in the oxygen
content in the installation room can occur,
therefore adequate ventilation must be
ensured. For this, the pellet stove offers you
the possibility of being able to be operated
independent of the room air. For this, connect
the air-intake connection piece situated at the
back (diameter: 50 mm, see Picture 1) with a
hose or similar, suitable air duct. The end of
the air duct must be located in the open air or
a well-ventilated room inside the building. For
the installation of the pellet stove in
combination with a controlled living-room
ventilation, the end of the incoming-air duct
must not be located in a room connected to
the air-network system. To guarantee an
adequate air supply, the line should not be
longer than approx. 3 m and not have too
many bends. This line should have a
minimum diameter of 5 cm (the more the
better). If the line is conducted into the open
air, it must end with a 90°-bend downwards or
with a windbreak (see Picture 4).
6


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Haas-Sohn COMPACT-PELLET 309 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Haas-Sohn COMPACT-PELLET 309 in the language / languages: English as an attachment in your email.

The manual is 3.71 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Haas-Sohn COMPACT-PELLET 309

Haas-Sohn COMPACT-PELLET 309 User Manual - German - 43 pages

Haas-Sohn COMPACT-PELLET 309 User Manual - French - 40 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info