10.2 Testing Devices in Accordance with DIN VDE 0701-0702
In accordance with DIN VDE 0701-0702 regulations, repaired or
modified electrical devices must provide users with the same de-
gree of safety against the dangers of electrical energy as is also
the case for new devices. The following tests must be executed in
the order specified below to this end:
1. Visual inspection
2. Protective conductor resistance
3. Insulation characteristics:
if technically reasonable, i.e. if the DUT does not include
any electrically actuated, all-pole switches:
– Insulation resistance followed by protective conductor
or equivalent leakage current
– Otherwise: leakage current during operation
(protective conductor current and contact current)
Safety extra-low voltage (only at point of connection
of safety extra-low voltage generated in the DUT)
4. Function test
5. Labeling inspection
6. Documentation
Visual inspection is performed before metrological testing is
executed, and includes the following points:
Damage to the connector cables
Damage to the insulation
Correct selection and use of cables and plugs
Condition of the mains plug, the connector terminals and wires
Defective cable bending guard
Defective connector cable stress relief
Condition of mounts, cable retainers, the fuse holder which is
accessible to the user etc.
Damage to the housing and the safety covers
Signs of overloading, as well as improper use or operation
Signs of impermissible tampering or modifications
Contamination, corrosion or aging which impermissibly impairs
safety
Contamination or clogging of openings required for cooling
Condition of air filters
Leak-proof containers for water, air or other media, condition
of pressure relief valves
Operability of switches, controllers, adjusting devices etc.
Legibility of all labels and symbols with safety functions, as well
as rated values
and position indicators
Good legibility of labeling required for safety
(e. g. warning symbols, protection class, characteristic fuse
data, switch positions for disconnectors).
133


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt SECUSTAR FM at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt SECUSTAR FM in the language / languages: English as an attachment in your email.

The manual is 1,75 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info