GMC-I Messtechnik GmbH 21
7.2.3 Testing RCCBS with 5 I
N
The measurement of time to trip is performed here with 5 times
nominal residual current.
Note
Measurements performed with 5 times nominal fault cur-
rent are required for testing type and G RCCBs in the
manufacturing process. They are used for personal
safety as well.
Measurement can be started with the positive half-wave at “0°” or
with the negative half-wave at “180°”.
Both measurements must nevertheless be performed. The longer
of the two tripping times is decisive regarding the condition of the
tested RCCB. Both values must be less than 40 ms.
Select Measuring Function
Set the Parameter – Start with Positive or Negative Half-Wave
Set the Parameter – 5 Times Nominal Current
Note
The following restrictions apply to the selection of tripping
current multiples relative to nominal current:
500 mA: 1 x, 2 x I
N
Start Measurement
7.2.4 Testing of RCCBs which are Suited for
Pulsating DC Residual Current
In this case, RCCBs can be tested with either positive or negative
half-waves. The standard calls for tripping at 1.4 times nominal
current.
Select Measuring Function
Set the Parameter – Positive or Negative Half-Wave
Set the Parameter – Test With and Without “Non-Tripping Test”
Non-Tripping Test
If, during the non-tripping test which lasts for 1
second, the RCD trips too early at 50% I
N
, i.e.
before the actual tripping test starts, the pop-up
window shown at the right appears.
Note
The following restriction applies to the selection of trip-
ping current multiples relative to nominal current: Double
and five-fold nominal current is not possible in this case.
Note
According to DIN EN 50178 (VDE 160), only type B
RCCBs (AC-DC sensitive) can be used for equipment
with > 4 kVA, which is capable of generating smooth DC
residual current (e.g. frequency converters).
Tests with pulsating DC fault current only are not suitable
for these RCCBs. Testing must also be conducted with
smooth DC residual current in this case.
Note
Measurement is performed with positive and negative
half-waves for testing RCCBs during manufacturing. If a
circuit is charged with pulsating direct current, the func-
tion of the RCCB can be executed with this test in order
to assure that the RCCB is not saturated by the pulsating
direct current so that it no longer trips.
S
I
N
Negative direct current
Positive direct current
Waveform:
180°: Start with neg. half-wave
0°: Start with pos. half-wave
5 times tripping current
X times tripping current:
I
N
Neg. half-wave
Pos. half-wave
Negative direct current
Positive direct current
Waveform:
X times tripping current:
50% I
N
*
* Non-tripping test
with 50% I
N
21


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt PROFITEST MXTRA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt PROFITEST MXTRA in the language / languages: English as an attachment in your email.

The manual is 2,28 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Gossen Metrawatt PROFITEST MXTRA

Gossen Metrawatt PROFITEST MXTRA User Manual - Dutch - 92 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info