7.2 Special Testing for Systems and RCCBs
7.2.1 Testing Systems and RCCBs with Rising Residual Current
(AC) for Type AC, A/F, B/B+ and EV RCDs
Measuring Method
The instrument generates a continuously rising residual current of
(0.3 to 1.3) I
N
within the system for the testing of RCDs.
The instrument stores the contact voltage and tripping current
values which were measured at the moment tripping of the RCCB
occurred, and displays them.
One of contact voltage limit values, U
L
=25V or U
L
=50V/65V,
can be selected for measurement with rising residual current.
Select Measuring Function
Connection
Set Parameters for I
F
Start Measurement
Measuring Sequence
After the measuring sequence has been started, the test current
generated by the instrument is continuously increased starting at
0.3 times nominal residual current, until the RCCB is tripped. This
can be observed by viewing gradual filling of the triangle at I.
If contact voltage reaches the selected limit value (U
L
=65V, 50V
or 25 V) before the RCCB is tripped, safety shut-down occurs.
The U
L
/R
L
LED lights up red.
Note
Safety Shut-down: At up to 70 V, a safety shut-down is
tripped within 3 seconds in accordance with IEC 61010.
If the RCCB is not tripped before the rising current reaches nomi-
nal residual current I
N
, the RCD/FI LED lights up red.
Attention!
!
If bias current is present within the system during mea-
surement, it is superimposed onto the residual current
which is generated by the instrument and influences
measured values for contact voltage and tripping cur-
rent. See also section 7.1.
Evaluation
According to DIN VDE 0100, Part 600, rising residual current
must, however, be used for measurements in the evaluation of
RCDs, and contact voltage at nominal residual current I
N
must
be calculated from the measured values.
The faster, more simple measuring method should thus be taken
advantage of (see sectionl 7.1).
7.2.2 Testing Systems and RCCBs with Rising Residual Current
(AC) for Type B/B+ and EV RCDs (nur MTECH+, MXTRA &
SECULIFE IP)
In accordance with VDE 0413, part 6, it must be substantiated
that, with smooth direct current, residual operating current is no
more than twice the value of rated residual current I
N
. A continu-
ously rising direct current, beginning with 0.2 times rated residual
current I
N
, must be applied to this end. If current rise is linear, ris-
ing current may not exceed twice the value of I
N
within a period
of 5 seconds.
Testing with smoothed direct current must be possible in both
test current directions.
I
F
Nominal residual current:
Type 1: RCD, SRCD, PRCD etc.
Nominal current: 6 ... 125 A
Type 2: AC , A/F , B/B+ *
EV
* Type B/B+/EV = AC/DC sensitive
10 ... 500 mA
sine
Negative/positive half-wave
Waveform:
Connection:
without/with probe
System type:
TN/TT, IT
Negative/positive direct current
Contact voltage:
Tripping limit values:
20


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt PROFITEST MXTRA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt PROFITEST MXTRA in the language / languages: English as an attachment in your email.

The manual is 2,28 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Gossen Metrawatt PROFITEST MXTRA

Gossen Metrawatt PROFITEST MXTRA User Manual - Dutch - 92 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info