1) Measuring Contact Current Without Tripping the RCD
Measuring Method
The instrument uses a measuring current of only 1/3 nominal
residual current for the determination of contact voltage U
IN
which occurs at nominal residual current. This prevents tripping of
the RCCB.
This measuring method is especially advantageous, because
contact voltage can be measured quickly and easily at any electri-
cal outlet without tripping the RCCB.
The usual, complex measuring method involving testing for the
proper functioning of the RCD at a given point, and subsequent
substantiation that all other systems components requiring pro-
tection are reliably connected at low resistance values to the
selected measuring point via the PE conductor, is made unneces-
sary.
N-PE Reversal Test
Additional testing is conducted in order to
determine whether or not N and PE are
reversed. The pop-up window shown at
the right appears in the event of reversal.
Attention!
!
Execute a data backup before starting measurement and
switch off all consumers in order to prevent the loss of
data in data processing systems.
Start Measurement
Amongst other values, contact voltage U
IN
and calculated earth-
ing resistance R
E
appear at the display panel.
Note
The measured earthing resistance value R
E
is acquired
with very little current. More accurate results can be
obtained with the selector switch in the R
E
position.
The DC + function can be selected here for sys-
tems with RCCBs.
Unintentional Tripping of the RCD due to Bias Current within the System
If bias currents should occur, they can be measured with the help
of a current clamp transformer as described in section 13.1 on
page 50. The RCCB may be tripped during the contact voltage
test if extremely large bias currents are present within the system,
or if a test current was selected which is too great for the RCCB.
After contact voltage has been measured, testing can be per-
formed to determine whether or not the RCCB is tripped within
the selected time limits at nominal residual current.
Unintentional Tripping of the RCD due to Leakage Current in the Measur-
ing Circuit
Measurement of contact voltage with 30% nominal residual cur-
rent does not normally trip an RCCB. However, the trip limit may
be exceeded as a result of leakage current in the measuring cir-
cuit, e.g. due to interconnected power consumers with EMC cir-
cuit, e.g. frequency converters and PCs.
2) Tripping Test after the Measurement of Contact Voltage
Press the
I
N
key.
The tripping test need
only be performed at
one measuring point for
each RCCB.
If the RCCB is tripped at nominal residual current,
the MAINS/NETZ LED blinks red (line voltage disconnected) and
time to trip t
a
and earthing resistance R
E
appear at the display
panel.
If the RCCB is not tripped at nominal residual current,
the RCD/FI LED lights up red.
Contact Voltage Too High
If contact voltage U
IN
, which has been measured with 1/3 nomi-
nal residual current I
N
and extrapolated to I
N
, is > 50 V (> 25 V),
the U
L
/R
L
LED lights up red.
If contact voltage U
IN
exceeds 50 V (25 V) during the measuring
sequence, safety shut-down occurs.
Note
Safety Shut-down: At up to 70 V, a safety shut-down is
tripped within 3 seconds in accordance with IEC 61010.
Contact voltages of up to 70 V are displayed. If contact voltage is
greater than 70 V, U
IN
> 70 V is displayed.
Limit Values for Allowable, Continuous Contact Voltage
The limit for allowable, continuous contact voltage is U
L
=50V for
alternating voltages (international agreement). Lower values have
been established for special applications (e.g. medical applica-
tions: U
L
=25V).
Attention!
!
If contact voltage is too high, or if the RCCB is not
tripped, the system must be repaired (e.g. earthing resis-
tance is too high, defective RCCB etc.)!
3-Phase Connections
For proper RCD testing at three-phase connections, the tripping
test must be conducted for one of the three phase conductors
(L1, L2 and L3).
Inductive Power Consumers
Voltage peaks may occur within the measuring circuit if inductive
consumers are shut down during an RCCB trip test. If this is the
case, the test instrument may display the following message: No
measured value (– – – ). If this message appears, switch all power
consumers off before performing the trip test. In extreme cases,
one of the fuses in the test instrument may blow, and/or the test
instrument may be damaged.
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt PROFITEST MXTRA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt PROFITEST MXTRA in the language / languages: English as an attachment in your email.

The manual is 2,28 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Gossen Metrawatt PROFITEST MXTRA

Gossen Metrawatt PROFITEST MXTRA User Manual - Dutch - 92 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info