3.4 Analog Display
Logarithmic representation of the upper resistance scale allows for quick
recognition of the magnitude involved.
In order to achieve the required accuracy for testing of protective mea-
sures, the RANGE key allows for switching to the expanded lower limit
measuring range of 100 k ... 100 M.
The orange colored LEDs, (4) and (5), at the right end of the scale indicate
which of the two resistance measuring ranges is currently active.
The indicator LED lights up green to confirm correct insulation mea-
surement. If this LED does not light up, test voltage has not been
achieved. In this event a battery test is advisable.
The two lower scales are for voltage measurement and battery testing;
see Chapter 3.2.
4 Direct and Alternating Voltage Measurements
Direct voltages and sinusoidal alternating voltages with frequencies rang-
ing from 15 to 500 Hz can be measured with the tester. Deflection of the
needle at the instrument is always positive for direct voltage measure-
ments, regardless of polarity at the connections. Alternating voltage is
indicated as an effective value.
Voltage measurements are used to test for the absence of voltage prior to
insulation resistance measurements, as well as for the automatic dis-
charge of capacitive devices under test. The voltage drop can be
observed at the display.
Note
Voltage measurement can always be performed with the function
selector switch in the “V” position, regardless of the position of the
range selector switch (even without batteries).
Ð Set the function selector switch to the “V” position.
Ð Check to see that the needle points to “0” in the V scale when the test
prods are not connected. Reset the needle as required with the ad-
justor screw for mechanical zero adjustment.
Ð
The position of the range selector switch has no influence on voltage mea-
surements, although we recommend setting it to the OFF/V position.
Ð Contact the measuring points with both test prods.
Ð Read the measurement value at the V scale.
Note
Voltages of greater than 2000 V may not be applied. Input resis-
tance for the voltage measuring range is equal to 5 M
5 Insulation Resistance Measurement
Be certain that the device under test is voltage-free before performing
measurements; see Chapter 4.
For measurements within a range of 100 G (10 G) ... 1 T the guard
cable should be used; see Chapter 5.3, page 8.
5.1 Measurement Procedure
Ð Set the function selector switch to the position, in order to activate
test voltage.
Ð A range of either 10 k ... 1 T or 100 k ... 100 Mcan be pre-se-
lected with the RANGE key.
Ð Select the required nominal voltage of 100 V, 250 V, 500 V, 1000 V,
1500 V, 2000 V, 2500 V or 5000 V with the range selector switch de-
pending upon the nominal voltage of the DUT.
When lit, the LED (4) indicates that the upper limit measuring range of
10 k ... 1 T has been activated.
Ð Contact the measuring point with both test prods and wait until the
needle has come to rest. Depending upon the DUT this might take
only a few, or up to 30 seconds, if, for example, large capacities (long
cables) must be charged.
Ð Read the measurement value from the upper scale.
If the indicator LED (3) lights up green, the insulation measurement
is valid. If this LED does not light up, test voltage has not been
achieved. In this event a battery test is advisable; see Chapter 3.2,
page 5.
Ð In order to achieve the required accuracy for testing of protective
measures, select the high resolution range, 100 k ... 100 M, with
the help of the RANGE key. The LED (5) lights up.
Ð Contact the measuring point with both test prods once again.
Ð Read the measurement value from the lower scale.
6


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt METRISO PRIME at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt METRISO PRIME in the language / languages: English as an attachment in your email.

The manual is 0,31 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Gossen Metrawatt METRISO PRIME

Gossen Metrawatt METRISO PRIME User Manual - German - 14 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info