3.3.2 Insulation Resistance Measurement
Switch insulation measurement on by pressing the RISO/USPD
key.
Figure 3.7: Setting Test Voltage
Select the required measuring voltage with the help of the
UTEST and UTEST keys. By briefly pressing the respective
key, voltage is increased or decreased to one of the following
nominal values: 50, 100, 250, 500 or 1000 V. The selected
test voltage appears at the display in the U
TEST field. For indi-
vidualized value settings, press and hold either the
UTEST or
UTEST key until the value can be changed in 1 V steps
within a range of 50 to 1000 V. The desired value is then se-
lected by once again briefly pressing the respective key. Sev-
eral seconds after one of these two keys has been activated
for the last time, the test instrument is returned to the mode
which allows for switching amongst nominal values of 50,
100, 250, 500, 1000 V only.
Contact the device under test with both test probes.
Figure 3.8: Connection Example
If an interference voltage of greater than about 10 V is
present in the measured electrical circuit, its value is dis-
played and the START key is disabled (see section 3.3.1
on page 4). Eliminate the source of interference voltage
before continuing with the measurement.
Trigger measurement by pressing the START key. Release the
key as soon as measurement is started.
Rising measuring voltage is displayed by means of a bar
graph (this may take several tens of seconds in the case of
large capacitances). At the same time, the value appears at
the display in the UIN field. The measuring cycle is ended auto-
matically.
If measurement needs to be continued for a longer period
of time, the START key has to be pressed and held for the
entire duration.
In contrast to this, the automatic cycle can be ended pre-
maturely by briefly pressing the START key. No results are
displayed in this case.
Read the measured insulation resistance value.
Note
The device under test may not be disconnected from the
test instrument as long as the “!” warning symbol is lit up.
Discharging large capacitances may take several tens of
seconds!
Note
Whistling or hissing noises may emanate from the test
instrument during measurement.
3.3.3 Measurements at Varistors (surge protection devices)
For this measuring function, the test instrument generates a rising
direct voltage within a range of 50 to 1000 V and, at the same
time, measures current flowing through the device under test. As
soon as current reaches a level of 1 mA, voltage is no longer
increased and the voltage value for the so-called milliampere
point appears at the display. In accordance with the respective
function which has been selected with the FUNC key, results for
overcurrent protection devices are also evaluated automatically
and listed as shown in the following table.
Note
If the DCMAX function has been selected, the upper voltage
limit for automatic results evaluation can be adjusted with the
UTEST and UTEST keys.
If the DCMIN function has been selected, the lower voltage
limit for automatic results evaluation can be adjusted with the
UTEST and UTEST keys.
For actual measurement or evaluation, it doesn’t matter which of
these two functions is selected, i.e. either DCMAX or DCMIN.
* Table for Surge Protection Device
If the SPD LIST function is selected (SURGE PROTECTION DEVICE
TABLE), a specific type and manufacturer/distributor is suggested
at the display, voltage at the milliampere point is displayed and
further information may appear as well.
The required type of surge protection device can be selected with
the
UTEST and UTEST keys.
Switch to off position!
Figure 3.9: Sample Results for an
Insulation Measure-
ment (the DUT is
being discharged)
Figure 3.10: Insulation Measure-
ment Results (the DUT
has been fully
discharged: U
IN = 0 V)
Symbol in the Display and its Meaning
Selected function
DC Voltage at the milliampere point
is measured
Voltage at the milliampere point
is outside of the measuring
range
DCMAX
DCMIN
Voltage at the milliampere point
is within the specified range
Voltage at the milliampere point
is outside of the specified range
SPD LIST * Voltage at the milliampere point
is within the specified range for
the selected type of surge pro-
tection device
Voltage at the milliampere point
is outside of the specified range
for the selected type of surge
protection device
USER
USER
USER
USER
5


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt METRALINE ISO-CHECK at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt METRALINE ISO-CHECK in the language / languages: English as an attachment in your email.

The manual is 0,39 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Gossen Metrawatt METRALINE ISO-CHECK

Gossen Metrawatt METRALINE ISO-CHECK User Manual - Dutch - 8 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info