412 Operator And
455 D Control Panel Installation Manual
THE 455 D CONTROL PANEL INSTALLATION INSTRUCTIONS
The procedure has ended and the gate is ready to
operate, using default slow down automatically set
by the control panel.
COMPLETE LEARNING
NOTES:
If only one gate operator (1) is used, you
must go through the entire programming
procedure, as if you were programming a
gate operator (2). When the gate operator
(1) has finished opening, supply 5 open
commands until the gate operator begins
to close, and then resume normal
operations.
Close the gates, enter “B
ASIC PROGRAMMING, select
the TIME LEARNING function and press the + push-
button for more than 3 seconds: the display begins
flashing and leaf 1 begins opening movement. The
following functions can be commanded by the OPEN
A command (by radio control or key push-button):
When gate operator (1) reaches the
position that you want it to slow down, an
open command must be given to start the
slow down phase. When the gate operator
reaches its positive stop, the operator will
automatically shut off.
An open command must be given to start
opening gate operator (2).
When gate operator (2) reaches the
position that you want it to slow down, an
open command must be given to start the
slow down phase. When the gate operator
reaches its positive stop, the operator will
automatically shut off.
An open command must be given to start
closing gate operator (2).
When gate operator (2) reaches the position
that you want it to slow down, an open
command must be given to start the slow
down phase. When the gate operator reaches
its positive stop, the operator will
automatically shut off.
An open command must be given to start
closing gate operator (1).
When gate operator (1) reaches the position
that you want it to slow down, an open
command must be given to start the slow
down phase. When the gate operator reaches
its positive stop, the operator will
automatically shut off.
The display stops flashing and the gate is ready for
normal operation.
NOTES:
The open command to slow down the gate
should be given before the gate reaches the
positive stop to prevent the gate from hitting
the stop at full speed. The positive stop could
be mistaken for an obstacle and then upon
hitting it, the gate(s) would automatically
reverse on contact.
AUTOMATED SYSTEM TEST
When you have finished programming, check if the
system is operating correctly.
Most important of all, check that the force is adequately
adjusted and that the safety devices are operating
correctly.
If pressure adjustments on hydraulic operators are not
set before programming. It may need to be
reprogrammed for desired results.
23


Need help? Post your question in this forum.

Forumrules
1

Forum

faac-455

Reset search

  • Looking for set up program for 455A control board to FAAC 760 dual gate
    Submitted on 9-7-2023 at 01:41

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for FAAC 455 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of FAAC 455 in the language / languages: English as an attachment in your email.

The manual is 0,82 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of FAAC 455

FAAC 455 User Manual - Dutch - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info