Refer to local regulations in the country of use for anything that is not specifically covered in this manual. In Italy, refer to standards
UNI 10683 and UNI 10412-2, as well as the Ministerial Decree No. 37, ex Law No. 46/90, in addition to any Regional or Local
Health Authority regulations. If installing in a block of apartments, first consult the block administrator.
Verify compatibility with other devices
According to standard UNI 10683/2005, the thermo-stoves must NOT be installed in the same room as extractors, type A and B gas
appliances and, in any case, devices that diminish the ventilation inside the room.
Check electrical connections (POSITION THE SOCKET IN AN ACCESSIBLE PLACE)
The stove is equipped with a electrical power cable to be connected to a 230V 50 Hz socket, preferably with a magnetothermic switch.
Voltage variations exceeding 10% can damage the thermo-stoves (unless already installed, an appropriate differential switch must be
fitted). The electrical system must comply with law; particularly verify the efficiency of the earthing system. The power line must have
suitable cross-section for the thermo-stoves’s power.
Lack of efficiency of the "ground" circuit causes malfunction for which Edilkamin cannot be held responsible.
Positioning
The thermo-stoves must be level for it to function correctly. Verify the bearing capacity of the floor.
Fire prevention safety distances
The thermo-stoves must be installed in compliance with the following safety conditions:
- medium flammability items must be kept at a minimum distance of 20 cm from the sides and
back of the thermo-stoves
- highly flammable items must be kept at a minimum distance of 80 cm if placed in front of the
thermo-stoves
- if the thermo-stoves is installed on flammable flooring, a sheet of heat insulating material must
be placed on the floor. This must extend at least 20 cm from the sides and 40 cm from the front.
Flammable objects must not be placed above the thermo-stoves or at a distance that is any less
than the stipulated safety distances. If connected to wooden walls or other flammable materials,
the smoke exhaust pipe must be appropriately insulated with ceramic fibre or other similar
material.
Air inlet: to be mandatorily implemented.
The room where the thermo-stoves is placed must have an air inlet with a cross-section of at least 80 cm² so as to guarantee sufficient
air supply to the stove for combustion.
Smoke outlet
The discharge system must only be used for the thermo-stoves (the smoke cannot be discharged into a chimney flue used by other
devices).
The smoke is discharged through the 10 cm diameter outlet at the back of the thermo-stoves. A T-junction must be set up with a con-
densation collection stopper at the beginning of the vertical section. The thermo-stoves smoke discharge must be connected with
outside by means of steel or black pipes EN 1856 certified.
The pipe line must be hermetically sealed. The pipes must be sealed and insulated using materials that are resistant to high tempera-
tures (high temperature silicone or mastic). The only horizontal section allowed may be up to 2 m long. The horizontal section must
have a minimum inclination of 3% and a maximum of two 90° bends. If the outlet is not fitted into a chimney flue, a vertical section
of at least 1.5 m will be required, complete with a wind guard. The vertical duct can be internal or external. If the smoke channel is
outside, it must be insulated.
If the smoke channel is fitted inside a chimney flue, the latter must be suitable for solid fuel. If it is wider than 150 mm in diameter,
a pipe must be entered and the outlet sealed to the masonry. All sections of the smoke duct must be accessible for inspection.
INSTALLATION
Distance from flammable material
Floor protection
A: insulated steel chimney flu, Insulated
B: minimum height 1.5 m, and however beyond the eaves of the roof
C-E: air intake from outside (through section at least 80 cm²)
D: steel chimney flue inside existing masonry chimney flue
35


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Edilkamin ATLANTA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Edilkamin ATLANTA in the language / languages: English, German, Dutch, French, Italian, Spanish as an attachment in your email.

The manual is 4.03 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info