Commissioning English
9. Commissioning
9.1. Minimum tests
After the heating device has been fully installed and
connected, you can carry out a check to make sure it
is working correctly.
The following minimum tests must be carried out:
Isolation test with a voltage of at least 500 V. The
isolation resistance must be at least 0.5 MΩ.
Measurement of the power consumption.
Alternatively, a cold resistance measurement can
be carried out.
9.2. Re-installation
If a device has already been in operation, disassem-
bled and set up at a different location, all commission-
ing checks must be carried out again before heating
operation.
During the first charge of the storage heater after in-
stallation, the entire process, starting with the cold
state (room temperature) to the switch-off of the load
controller, must be monitored by a qualified specialist.
Determine the amount of energy used by the heating
device during this process in kWh. This must not be
more than 125% of the rated charging stated on the
rating plate.
NOTE
During installation, check that the thermal insulation
was not damaged during transport.
Damaged thermal insulation must be replaced with an
identical part before the heating device is used again!
9.3. Installer menu
The commissioning of the storage heater by the spe-
cialist takes place via the installer menu. First, the fol-
lowing entries must be made:
Current time, date
DST = summer/winter time switch,
Key tone on/off.
Once the entries have been made, the user main
menu appears. The timer times listed below are set at
the factory. They can be adjusted at any time.
The functions described below can be set in the in-
staller menu.
Calling up the installer menu
Hold down the Menu key. The display initially
switches to the CHARGING menu. Continue to hold
the key (for approx. 3 seconds in total). The display
switches to the main menu.
P9 - operation on central charge control
NOTE
No setting is required if the device is operated without
central charge control.
Press and hold the MENU, ENTER and BACK key
for approx. three seconds. PIN code 0000 flashes.
Confirm the PIN code four times with the ENTER
key. Display P9 flashes.
Select display P9. P9 flashes.
Press the ENTER key. OFF flashes.
Use the   keys to select ON. ON flashes.
Press the ENTER key. Display DC flashes.
NOTE
Display DC/AC stands for the control signal of the
central control device. Either DC or AC must be se-
lected depending on the type used.
Comfort 1 Comfort 2 Comfort 3 Comfort 4
06:30 -
09:30
11:00 -
13:00
15:00 -
17:00
18:00 -
21:00
No. Function Explanation
P9 Central charge
control
Yes/No,
If yes: AC/DC,
If AC: Duty cycle in percent
P10
External room
temperature con-
troller
Yes/No
P11 auxiliary heating Yes/No
P12 Release signal currently without function
P13 Release manual
Define time window for
manual release.
See “P12 - release signal”
on page 21.
P14
Reaction to failing
central charge
control signal
100% or 0% charge in case
of failing signal.
No. Function Explanation
45


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex VFE50K at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex VFE50K in the language / languages: English, German as an attachment in your email.

The manual is 4.11 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info