798308
28
Zoom out
Zoom in
Previous page
1/72
Next page
EN-8 452231.66.34 · FD 9912 www.gdts.one
English SIK 6TES - SIK 14TES
7.5 Electrical connection
7.5.1 General
All electrical connection work must be carried out by a trained
electrician or a specialist for the specified tasks in accordance
with the
installation and operating instructions,
country-specific installation regulations (e.g. VDE 0100),
technical connection conditions of the energy suppliers
and supply grid operators (e.g. TAB) and
local conditions.
To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain con-
nected to the power supply and the flow must be maintained
through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed. Therefore, depending on the internal resistance of
the measuring instrument, a voltage can also be measured
when the contacts are open. However, this will be much lower
than the line voltage.
Extra-low voltage is connected to controller terminals N1-J1 to
N1-J11; N1-J24 to N1-J26 and terminal strip X3. If, due to a
wiring error, the line voltage is mistakenly connected to these
terminals, the heat pump manager will be destroyed.
7.5.2 Electrical installation
1) The supply electric cable for the output section of the heat
pump (up to 4-core) are fed from the electricity meter of
the heat pump via the utility blocking contactor (if required)
into the heat pump (see heat pump operating instructions
for supply voltage).
Connection of the mains cable to the control panel of the
heat pump via terminal X1: L1/L2/L3/PE.
ATTENTION!
!
!
Ensure the rotary field is clockwise when connecting the
mains cables (if the rotary field is not clockwise, the heat
pump will not work properly, is very loud and may cause
damage to the compressor).
An all-pole disconnecting device with a contact gap of at
least 3 mm (e.g. utility blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping
for all external conductors must be installed in the power
supply for the heat pump (tripping current and characteris-
tic in compliance with the device information).
2) The three-core electric supply cable for the heat pump
manager (heating controller N1) is fed into the heat pump .
Connection of the control line to the control panel of the
heat pump via terminal X2: L/N/PE.
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a constant voltage. For this reason, it
should be tapped upstream from the utility blocking con-
tactor or be connected to the household current, as impor-
tant protection functions could otherwise be lost during a
utility block.
3) The utility blocking contactor (K22) with main contacts and
an auxiliary contact should be dimensioned according to
the heat pump output and must be supplied by the cus-
tomer.
The NO contact of the utility blocking contactor is looped
from terminal strip X3/G (24 V AC) to connector terminal
J5/ID3. CAUTION! Extra-low voltage!
4) The contactor (K20) for the immersion heater (E10) of
mono energy systems (HG2) should be dimensioned ac-
cording to the radiator output and must be supplied by the
customer. It is controlled (230 V AC) by the heat pump
manager via terminals X2/N and N1-J13/NO4.
5) The contactor (K21) for the flange heater (E9) in the hot
water cylinder should be dimensioned according to the ra-
diator output and must be supplied by the customer. It is
controlled (230 V AC) by the heat pump manager via termi-
nals X2/N and N1-J16/NO 10.
6) The contactors mentioned above in points 3, 4 and 5 are
installed in the electrical distribution system. Mains cables
for the installed heater must be laid and secured in accord-
ance with the valid standards and regulations.
7) All installed electric cables must have permanent wiring.
8) The auxiliary circulating pump (M16) is connected to N1-
J16/NO9 and X2/N. When using pumps where the switch-
ing capacity exceeds the output, a coupling relay must be
interposed.
9) The domestic hot water circulating pump (M18) is con-
nected to N1-J12/NO6 and X2/N. When using pumps
where the switching capacity exceeds the output, a cou-
pling relay must be interposed.
10) The return sensor (R2) is integrated into heat pumps for in-
door installation.
The heat pump manager is connected via the following ter-
minals: X3/GND and N1-J2/U2.
11) The external sensor (R1) is connected to terminals X3/GND
and N1-J2/U1.
12) The domestic hot water sensor (R3) is included with the
domestic hot water cylinder and is connected to terminals
X3/GND and N1-J2/U3.
7.5.3 Connecting an electronically
regulated circulating pump
Electronically regulated circulating pumps have high starting
currents, which may shorten the service life of the heat pump
manager. For this reason, a coupling relay is installed or must be
installed between the output of the heat pump manager and
the electronically regulated circulating pump. This is not neces-
sary if the permissible operating current of 2 A and a maximum
starting current of 12 A are not exceeded in the electronically
regulated circulating pump or if express approval has been is-
sued by the pump manufacturer.
ATTENTION!
!!
It is not permitted to connect more than one electronically
regulated circulating pump via a relay output.
28


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex SIK 8TES at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex SIK 8TES in the language / languages: English, German, French as an attachment in your email.

The manual is 1.91 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info