798308
27
Zoom out
Zoom in
Previous page
1/72
Next page
www.gdts.one 452231.66.34 · FD 9912 EN-7
SIK 6TES - SIK 14TES English
7.4 Temperature sensor
The following temperature sensors are already installed or must
be installed additionally:
External temperature sensor (R1) supplied (NTC-2)
Return temperature heating circuit (R2) installed (NTC-10)
Flow temperature heating circuit (R9) installed (NTC-10)
Flow temperature primary circuit (R6) installed (NTC-10)
7.4.1 Sensor characteristic curves
The temperature sensors to be connected to the heat pump
manager must correspond to the sensor characteristic curve
illustrated in Fig. 7.2. The only exception is the external
temperature sensor included in the scope of supply of the heat
pump (see Fig. 7.3)
Fig. 7.2:Sensor characteristic curve NTC-10
Fig. 7.3:Sensor characteristic curve, NTC-2 according to DIN 44574 Ex-
ternal temperature sensor
7.4.2 Mounting the external temperature
sensor
The temperature sensor must be mounted in such a way that all
weather conditions are taken into consideration and the
measured value is not falsified.
Mount on the external wall on the north or north-west side
where possible
Do not install in a “sheltered position” (e.g. in a wall niche or
under a balcony)
Not in the vicinity of windows, doors, exhaust air vents,
external lighting or heat pumps
Not to be exposed to direct sunlight at any time of year
-
7.4.3 Installing the strap-on sensor
It is only necessary to mount the strap-on sensors if they are
included in the scope of supply of the heat pump but have not
yet been installed.
The strap-on sensors can be fitted as pipe-mounted sensors or
installed in the immersion sleeve of the compact manifold.
Mounting as a pipe-mounted sensor
Remove paint, rust and scale from heating pipe.
Coat the cleaned surface with heat transfer compound
(apply sparingly).
Attach the sensor with a hose clip (tighten firmly, as loose
sensors can cause malfunctions) and thermally insulate.
7.4.4 Hydraulic distribution system
The compact manifold and the dual differential pressureless
manifold function as an interface between the heat pump, the
heating distribution system, the buffer tank and, in some cases,
even the hot water cylinder. A compact system is used to
simplify the installation process, so that a lot of different
components do not have to be installed individually. Further
information can be found in the relevant installation
instructions.
Compact manifold
The return sensor can remain in the heat pump, or should be
installed in the immersion sleeve. The remaining empty space
between the sensor and the immersion sleeve must be filled
completely with heat transfer compound.
dual differential pressureless manifold
In order for the heating circuit pumps of the generator and con-
sumer circuits to supply the flow to the return sensor, this must
be installed in the immersion sleeve of the dual differential
pressureless manifold.
Temperature in °C -20 -15 -10 -5 0 5 10
NTC-2 in k14.6 11.4 8.9 7.1 5.6 4.5 3.7
NTC-10 in k67.7 53.4 42.3 33.9 27.3 22.1 18.0
15 20 25 30 35 40 45 50 55 60
2.92.42.01.71.41.11.00.80.70.6
14.9 12.1 10.0 8.4 7.0 5.9 5.0 4.2 3.6 3.1
0
10
20
30
40
50
60
70
-20-15-10-5 0 5 1015202530354045505560
External temperature in [°C]
Resistance value in [kOhm]
0
2
4
6
8
10
12
14
16
18
20
-20-15-10-5 0 5 1015202530354045505560
External temperature in [°C]
Resistance value in [kOhm]
Dimensioning parameter sensor lead
Conductor material Cu
Cable-length 50 m
Ambient temperature 35 °C
Laying system B2 (DIN VDE 0298-4 /
IEC 60364-5-52)
External diameter 4-8 mm
Hose clip
Strap-on sensor
Thermal insulation
27


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex SIK 8TES at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex SIK 8TES in the language / languages: English, German, French as an attachment in your email.

The manual is 1.91 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info