De Dietrich Gas 310/610 ECO
13.2.8
T
from control stops point to start point
Parameter , adjustable from 9 to 36°F [5 to 20°C]
This value sets the flow temperature at which the boiler will cut back in after a control stop.
The boiler will always goes to a control stop when the flow temperature equals the flow set-point temperature >
+9°F [> +5°C] The
T defines when the burner is switched on again. A value of 18°F [10°C] indicates the
temperature has to drop 9°F [5°C] below the calculated flow temperature set point before the boiler starts to run
again, cut back in temperature = flow set-point (80) + 5 parameter (10), i.e. 176 + 9 18 = 167°F [80 + 5
10 = 75
°
C]
13.2.9 Maximum flue gas temperature ()
Parameter , adjustable between 176 and 248°F [80 and 120°C] This value sets the maximum operating flue
gas temperature non metallic vent flue systems.
13.2.10 High limit temperature setting ()
Parameter , adjustable between 194 - 230°F [90 - 110°C] This value sets the high limit temperature at which
the boiler will shutdown in a lockout condition requiring manual intervention.
Important!! If the factory setting is reduced, a corresponding reduction in flow set-point will be required
otherwise the min. flow rate may be affected.
13.2.11 Modulation start point at T ()
Parameter , adjustable between 18 and 54°F [10 and 30°C] this value sets the flow/return
T
point at which the
control modulation begins. The boiler starts to modulate at the set-point and will be at minimum output if the
T
continues to rise to 72°F [40°C]. At 81°F [45°C]
T
the boiler will shut-off (shut-off code ). For
installations with low flow rates the starting point modulation can be brought forward (i.e. 27°F [15°C]), closer
matching boiler output to system demand. In systems with small volume flows the modulation start point can be
brought forward. The boiler is better equipped to anticipate low heat demand. The factory set-point should be
correct for most installations. The setting start point should only be changed if absolutely necessary.
13.2.12 Minimum water pressure ()
Parameter , adjustable between 0 58 psi [0 – 4 bar]. This setting only applies if an optional hydraulic pressure
sensor has been connected. This value sets the point at which the boiler will shut-down if the system pressure
falls below it. The boiler will resume normal operation when pressure is restored.
13.2.13 Adjustments options/accessories/units ()
Parameter is adjustable between 0 and 31. This setting is only applicable if options from table 17 are
connected to the boiler. The control unit detects which options have been connected by means of the value of
this parameter and adjusts the boiler control on this basis.
The required feedback message (as output in % or as temperature is °F or °C) can also be selected here if the
(standard) analog output is used. A list of values that have been assigned to specific options can be found in
Adding together the values of the options used gives the parameter setting
Fig 27 temperature control via analog (0-10v)
57


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for De Dietrich Gas 610 ECO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of De Dietrich Gas 610 ECO in the language / languages: English as an attachment in your email.

The manual is 3,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info