De Dietrich Gas 310/610 ECO
Gas 610 Temperature based 68 194
o
F [20-90
o
C] set the value of the boiler control operation
parameter to . To set the ratio between voltage and the desired flow temperature (see par. 13.2.5
and fig. 21)
0 to 0.9 Volt = boiler off
1 Volt = Flow temperature set point 50
o
F [10
o
C]
8 Volts = Flow temperature set point 176
o
F [80
o
C]
Output basedfixed parameters (20 to 100%), set the value of the boiler control setting parameter
to (see fig. 22)
8.6.6 2-Stage control (2 X no volt switched relays)
The heat output on each boiler module stages between the minimum and the maximum value based on
the set flow temperature, terminal connections X29-9 and X29-10. Set the value of each boiler control
operation parameter to (on/off).
8.6.7 4-Stage High/low control (4 x no volt switched relays)
The heat output is controlled between part load (50%, adjustable) and full load by means of a 4-stage
controller, terminal connection X29-9 and X29-10 low fire; X29-7 and X29-8 high fire.
Set the
value of each boiler control operation parameter to . The output percentage on which the
boiler runs on low fire can be adjusted with parameter (low fire start point as percentage) in the setting
mode. The ‘high fire’ percentage is dependent of the maximum adjusted output, see setting mode,
parameter
(maximum output). During this ‘high’ state modulation on adjusted flow temperature is
released.
8.7 Other inputs
8.7.1 Shut down input
As standard each boiler module is supplied with a shut down interlock carrying a 24 Volt AC boiler control
circuit. This input does not require manual re-set.
Any external devices required to stop the boiler (e.g. limit switches of throttling valves, minimum gas
pressure switches) should be wired in series and connected to terminals X29-5 and X29-6, breaking the
circuit will activate the safety interlock and put the boiler into a shut-off condition with code . If
this input is being used, the wire bridge must first be removed.
8.7.2 Lock-out input
As standard each boiler module is supplied with a lock out interlock carrying a 24 Volt AC boiler control
circuit. This input requires manual re-set if activated.
Any external devices required to stop the boiler (e.g. maximum gas pressure switch) must be volt free and
should be wired in series and connected to terminals X29-1 and X29-2. Breaking the circuit will activate
the safety interlock and put the boiler into a lock out condition, failure code  requiring manual
intervention to re-set it. If this input is being used, the wire bridge must first be removed.
8.7.3 External interlock
As standard each boiler module is supplied with an external interlock carrying a 24 Volt AC boiler control
circuit.
Any external devices required to prevent the boiler from operating (e.g. boiler room ventilation air flow
switch, or butterfly valve end switch) must be volt free and should be wired in series and connected to
terminals X29-3 and X29-4, breaking the circuit will prevent the boiler from starting. Boiler does not go to
lock-out. If this interlock is being used, the wire bridge must first be removed.
38


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for De Dietrich Gas 610 ECO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of De Dietrich Gas 610 ECO in the language / languages: English as an attachment in your email.

The manual is 3,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info