De Dietrich Gas 310/610 ECO
8.6.2 Gas 310 Modulating controls general
(2 wire control)
To make full use of the boiler’s modulating feature, a 0-10v [dc] input control will be needed.
Some controls can provide weather compensation to achieve maximum efficiency and minimum boiler cycling
whilst maintaining design condition within the building.
A. Modulating boiler control [single boiler]
An optional optimizing weather-compensated boiler control can be
used for single boilers. The compensator can regulate the boiler
output against outside weather conditions, and provide time and
temperature control over the DHW. The compensator is mounted
in a reference room (uses an internal sensor to monitor room
temperature) and is interfaced to communicate with the boiler’s
controls via the two wire serial interface. On site connection of the
outside and common flow sensors complete the... Set the value
of the boiler control
Operation parameter to .
Note: Please refer to the control documentation for installation requirements.
B. Modulating multiple boiler controller
An optimizing, weather-compensated boiler control can be used to
control multiple boilers. The compensator can regulate the boiler
output against outside weather conditions, and provide time and
temperature control over the DHW. The multiple boiler control-
compensator is mounted centralized and can be interfaced to
communicate with the boiler’s control the supplied adapter. On site
connection of the outside and common flow sensors complete the
installation. Set the value of the boiler control operation
parameter to .
Note: Please refer to the control documentation for installation
requirements.
Fig. 22 °output control via analog (0-10 Volt) signal
8.6.3 BMS Analog control (0-10 Volt DC)
Input resistance R
im
= 66 k.
The heat output modulates between the minimum and the maximum value on the basis of the voltage supplied by
an external analog (0-10V) input. To control the boiler with an analog signal, the signal has to be connected on
terminals X29-11 (+) and X29-12 (-) of the terminal strip in the instrument panel.
Important!!! When analog control is opted, the on/off –contact and the high/low –contact have higher priority
(e.g. frost protection
).
Fig. 21 Temperature control via analog (0-10 Volt) signal
36


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for De Dietrich Gas 610 ECO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of De Dietrich Gas 610 ECO in the language / languages: English as an attachment in your email.

The manual is 3,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info