71Fault elimination
Code Message Information
Warning Fault Possible causes Remedy
––– E22 Max. Filling Time The Condair RS is monitoring the lling process with different levels which have
to be reached within a preset time during lling. If a certain level is not reached
within the preset time the fault message "Max. Filling Time" is triggered.
Note: the inlet valve remains open. .
Water feed blocked, shut-off valve in
the water supply line closed, lter valve
closed or blocked).
Water pressure too low.
Check water feed (lter, pipes, etc.),
check/open shut-off valve, Check water
pressure.
Inlet valve blocked or defective. Check strainer inside the inlet valve,
clean if necessary. Replace valve.
Excessive back pressure in the steam
line (duct pressure too high, steam line
too long or kinked), causing water loss
via lling cup.
Check duct pressure, inspect steam
installation. If applicable install pressure
compensation kit (available as option).
water system leaky. Check/seal water system.
––– E26 ** Contactor Jammed There is voltage on the power board, even though the main contactor is not activated!
Main contactor jammed. Check the main contactor and replace
it if necessary.
W28 E28 Small maintenance The maintenance interval for the "Small maintenance" has elapsed. If the "Small
maintenance" is not performed and the maintenance message is not reset within
one week after the maintenance message has been triggered a fault message
is triggered!
Note: The Condair RS remains operable. The maintenance message is shown
until the maintenance counter is reset.
"Small maintenance" due. Perform "Small maintenance" and reset
maintenance counter.
W29 E29 Extended mainte-
nance
The maintenance interval for the "Extended maintenance" has elapsed. If the
"Extended maintenance" is not performed and the maintenance message is not
reset within one week after the maintenance message has been triggered a fault
message is triggered!
Note: The Condair RS remains operable. The maintenance message is shown
until the maintenance counter is reset.
"Extended maintenance" due. Perform "Extended maintenance" and
reset maintenance counter.
––– E32 Demand Snsr Demand signal invalid, humidication is stopped!
Humidity sensor or external controller
not or not correctly connected.
Check/correctly connect humidity sen-
sor/external controller.
Sensor/controller wrong congured (e.g.
mA signal instead of V signal set).
Correctly congure sensor/controller via
the conguration menu.
Sensor/controller defective. Replace sensor/controller.
––– E33 Limit.Snsr Signal of the external limiter controller invalid, humidication is stopped!
Limiter controller not or not correctly
connected.
Check/correctly connect limiter con-
troller.
Limiter controller wrong congured (e.g.
mA signal instead of V signal set).
Correctly congure limiter controller via
the conguration menu.
Limiter controller defective. Replace limiter controller.
W34 E34 Max. Drain Time The level in the steam cylinder has not dropped to the preset level within
the preset time. The Condair RS carries out a level test. This procedure is
repeated three times if maximum drain time is exceeded again, then a fault
message is triggered and humidication is stopped!
Drain pump not or not correctly con-
nected.
Check/correctly connect drain pump.
Drain hose inside the unit kinked or
blocked.
Check/Cclean drain hose inside the unit,
replace if necessary.
water drain obstructed (external drain
line or funnel blocked.
Clean external drain line and funnel.
Hoses to level unit blocked. Clean or replace hoses.
Drain pump defective. Replace drain pump.
71


Need help? Post your question in this forum.

Forumrules
1

Forum

condair-rs

Reset search

  • why drain hose led to left, is it due to electrical on right side.
    Submitted on 29-8-2022 at 23:32

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Condair RS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Condair RS in the language / languages: English as an attachment in your email.

The manual is 5,11 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Condair RS

Condair RS Installation Guide - English - 80 pages

Condair RS User Manual - Dutch - 80 pages

Condair RS Installation Guide - Dutch - 76 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info