Service level menu (for qualified heating engineers only)
7
7.5.9 Return boost cut-out temperature differential
Menu: Service > Settings > Reserve bypass cut-out temperature differential
When the temperature difference between the solar storage cylinder and the thermal system return
drops to the set figure, the return boost valve is closed.
The minimum difference from the cut-in temperature difference is 3 K ( °C).
7.5.10 Heat meter
Menu: Service > Settings > Heat meter
Switches the yield calculation function on or off. The heat quantity is calculated and totalled up by
means of a volumetric flow meter (1 pulse/litre) and the difference between the flow and return tem-
peratures. The heat usage for the current twenty-four hour period can also be viewed.
When a heat meter is used, the glycol content must be set.
7.5.11 Glycol content
Menu: Service > Settings > Glycol content
In order to obtain accurate readings from the heat meter, the glycol content of the solar fluid must
be specified.
Setting range Default range setting New setting
3 - 17 K (°C) 3 K (°C)
Tab. 22
Setting range Default range setting New setting
Yes/No No
Tab. 23
Setting range Default range setting New setting
0 %, 30 %, 40 %,
45%, 50 %
50 %
Tab. 24
59


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Buderus Logamatic SC40 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Buderus Logamatic SC40 in the language / languages: English as an attachment in your email.

The manual is 1,87 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Buderus Logamatic SC40

Buderus Logamatic SC40 Usermanual and installation guide - German - 76 pages

Buderus Logamatic SC40 User Manual - Dutch - 16 pages

Buderus Logamatic SC40 Installation Guide - Dutch - 76 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info