Rego 1000 – 6 721 831 662 (2021/03) en
12
Settings Customer level
External control
Set point value calculation
The set point value for the heating circuit is the current curve value
adjusted with active curve influence, if any such exists.
Priority order for curve influence is:
External control
Active program
Holiday
Only one of these can be active. How big the influence should be and
when to exercise it is set in the respective function.
Fixed set point value
A fixed set point value (not curve-based) applies in the event of:
External set point value. The set point value is determined according
to input signal 0-10V where 1V is 10 °C and 10V is 80 °C (0V triggers
an alarm).
Set point value limitation
The calculated set point value is always checked against the permitted
temperature limits.
The applicable set point value T1 for Circuit 1 and the measured actual
value for T1 are used to activate and deactivate the heat demand.
The following applies to Circuit 2, 3...: When the actual value for the
mixed circuit's T1 is low in relation to the set point value, more heating
water is shunted into the circuit so as to maintain the set point value.
If the flow temperature has been below the set point value for a certain
period of time, there is heat demand and the compressor produces heat
before there is a too significant temperature reduction indoors. This
happens until the flow temperature is a couple of degrees higher than
the set point value. (Or because Maximum operating time for heating
at hot water demand has passed.)
Heating demand is not active during summer operation.
1.10 General
1.10.1 Summer/winter time
1.10.1.1 Winter operation
If On is selected, the heat pump is constantly in winter operation and
heat and hot water are always produced. Off signifies constant summer
operation; only hot water is produced. Automatic signifies change-over
at the set outdoor temperature.
1.10.1.2 Outdoor temperature limit for change over
The menu is displayed only if Automatic selected in 1.10.1.1 Winter
operation .
6.3 Hot water
Under 2 Hot water there are functions to:
Select operating mode
•Request 2.3 Extra hot water
•Specify when 2.4 Hot water peak must be performed in order to
eliminate bacteria.
•Set any 2.5 Hot water program
2.2 Hot water mode
Select hot water mode.
Economy means that the hot water is permitted to cool slightly
before hot water production starts compared to Comfort . Heating
stops at a slightly lower temperature.
▶Change to Comfort If more or hotter hot water is desired.
This setting must be used if electric additional heat is missing or if the
hot water circulation is used, when the temperature in the hot water
circulation is otherwise too low.
The factory settings for on and off temperature are approx. 8 K ( °C)
lower in Economy mode compared to Comfort mode. These values can
be adjusted by the installer.
2.3 Extra hot water
Additional amount of hot water is produced by temporarily increasing
the temperature of the hot water during the set number of hours to the
indicated stop temperature.
2.3.1 Extra hot water duration
Set the duration of extra hot water production.
2.3.2 Extra hot water stop temperature
Set the stop temperature for extra hot water.
The heat pump starts the function directly and uses the compressor first
and then the additional heat source to increase the temperature. When
the desired number of hours have passed, the heat pump returns to
normal hot water mode.
2.4 Hot water peak
Hot water peak means a temporary increase in the hot water
temperature to approx. 65 °C for thermal elimination of bacteria
(pasteurisation).
For the hot water temperature increase, the compressor is used first;
the additional heat source then continues alone.
2.4.1 Day of the week
Set the day when hot water peak should happen. None means that
the function is deactivated. All means that a hot water peak takes
place every day.
If hot water peak is deactivated comfort mode must be selected in the
menu 2.2 Hot water mode .
2.4.2 Interval in weeks
Set how often a hot water peak should take place.
1 means a hot water peak every week.
2 means that a hot water peak takes place in all even weeks of the
year, i.e., in week 2, 4, 6, etc.
3 means week 3, 6, 9, etc.
4 means week 4, 8, 12, etc.
2.4.3 Start time
Set time for the hot water peak.
2.5 Hot water program
Program 1 and Program 2 enables you to block hot water production
during the set time.
2.5.1 Active program
2.5.2 View/edit active program
The menu is only displayed if Program 1 or Program 2 is selected.
Programs are changed in the same way as for 1.1.11 Room
temperature program .
In the event of alternation between winter and summer
operation and vice versa, there is a certain delay aimed
at preventing constant starting and stopping of the
compressor when the outdoor temperature oscillates
around the temperature limit.
DANGER: Risk of burn injuries.
Use a mixing valve when the hot water temperature
exceeds 60 °C.
WARNING: Risk of scalding.
At hot water temperatures greater than 60 °C, there is a
risk of scalding.
Exercise caution when using hot water immediately
after a hot water peak.
12


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Rego 1000 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Rego 1000 in the language / languages: English as an attachment in your email.

The manual is 4.13 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info