Commissioning | 35
6 720 815 257 (2014/10)MS 200
Transfer
Solar DHW
4.5.2 Start solar thermal system
Menu item Adjustment range Function description
Transfer start diff. 6 ... 10 ... 20 K If the differential set here between cylinder 1 and cylinder 3 is exceeded and all conditions for switching on have
been met, the transfer pump is on.
Transfer stop diff. 3 ... 5 ... 17 K If the differential between cylinder 1 and cylinder 3 falls below the value set here, the transfer pump is off.
Start diff. diff. ctrllr 6 ... 20 K If the differential between the measured temperature at the heat source (TS14) and the measured temperature at
the heat sink (TS15) is above the set value, the output signal is on (only with Temp differential controller (R)).
Stop diff. diff. ctrllr 3 ... 17 K If the differential between the measured temperature at the heat source (TS14) and the measured temperature at
the heat sink (TS15) is below the set value, the output signal is off (only with Temp differential controller (R)).
Max source t. diff ctrllr 13 ... 90 ... 120 °C If the temperature at the heat source exceeds the value set here, the temperature differential controller switches off
(only with Temp differential controller (R)).
Min. source temp. Diff ctrl 10 ... 20 ... 117 °C If the temperature at the heat source exceeds the value set here and all conditions for switching on have been met,
the temperature differential controller switches on (only with Temp differential controller (R)).
Max setbck temp diff ctrl 20 ... 60 ... 90 °C If the temperature at the heat sink exceeds the value set here, the temperature differential controller switches off
(only with Temp differential controller (R)).
Table 21
WARNING: Risk of scalding!
If DHW temperatures above 60 °C are set or thermal
disinfection is switched on, a mixing valve must be
installed.
Menu item Adjustment range Function description
DHW controller act. Boiler One DHW system is installed and is controlled by the heat appliance.
2 DHW systems are installed. One DHW system is controlled by the heat appliance. The 2nd DHW system is
controlled by an MM 100 module (coding switch set to 10).
Thermal disinfection, reheating and solar optimisation only have an effect on the DHW system that is controlled by
the heat appliance.
external module 1
One DHW system is installed and is controlled by an MM 100 module (coding switch set to 9).
2 DHW systems are installed. Each DHW system is controlled by an MM 100 module (coding switch set to 9/10).
Thermal disinfection, reheating and solar optimisation only have an effect on the DHW system that is controlled by
external module 1 (coding switch set to 9).
external module 2
2 DHW systems are installed. One DHW system is controlled by the heat appliance. The 2nd DHW system is
controlled by an MM 100 module (coding switch set to 10).
2 DHW systems are installed. Each DHW system is controlled by an MM 100 module (coding switch set to 9/10).
Thermal disinfection, reheating and solar optimisation only have an effect on the DHW system that is controlled by
external module 2 (coding switch set to 10).
Therm.dis./daily ht cyl1 Yes Switches thermal disinfection and daily heat-up of cylinder 1 on or off.
No
Therm.dis./daily ht cyl2 Yes Switches thermal disinfection and daily heat-up of cylinder 2 on or off.
No
Therm.dis./daily ht cyl3 Yes Switches thermal disinfection and daily heat-up of cylinder 3 on or off.
No
Daily heat start time 00:00 ... 02:00
... 23:45 h
Start time for daily heat-up. Daily heat-up ends after a maximum of 3 hours. Only available if the MS 200 module is
installed in a BUS system without a heat source (not possible with all user interfaces).
Daily heat temp. 60 ... 80 °C Daily heat-up ends once the set temperature is reached, or, if the temperature is not reached, after a maximum of
3 hours. Only available if the MS 200 module is installed in a BUS system without a heat source (not possible with all
user interfaces).
Table 22
Menu item Adjustment range Function description
Start solar thermal
system
Yes The solar system only starts up once this function has been enabled.
Before starting up the solar thermal system, you must:
Fill and vent the solar thermal system.
Check the parameters for the solar thermal system and, if necessary, adjust them to suit the installed system.
No
This function can be used to switch off the solar system for maintenance purposes.
Table 23
35


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch MS 200 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch MS 200 in the language / languages: English, German, Dutch, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 18,85 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info