Next page
Commissioning | 33
6 720 815 257 (2014/10)MS 200
Cylinder
Max. collector temp. 100 ... 120
... 140 °C
If the collector temperature exceeds the temperature set here, the solar pump is off.
Min. collector temp. 10 ... 20 ... 80 °C If the collector temperature falls below the temperature set here, the solar pump is off, even if all conditions for
switching on have been met.
Vac. tube pump anti-seize Yes The solar pump is switched on briefly every 15 minutes between 6:00 and 22:00 in order to pump the heated heat
transfer medium to the temperature sensor.
No Vacuum tube collector pump anti-seize function switched off.
Vac. tube pump anti-seize 2 Yes The solar pump 2 is switched on briefly every 15 minutes between 6:00 and 22:00 in order to pump the heated
heat transfer medium to the temperature sensor.
No
2nd vacuum tube collector pump anti-seize function switched off.
Southern Europe function Yes Frost Protection - if the collector temperature falls below the set value ( Start temp. S.Eur. fct.), the solar pump is
on. This pumps hot water from the cylinder through the collector. If the collector temperature exceeds the set
temperature by 2 K, the pump is off.
This function is intended solely for regions where the high temperatures mean that damage from freezing usually
cannot occur.
Caution! This function is not a substitute for glycol within the solar circuit!
No
Mediterranean climate function switched off.
Start temp. S.Eur. fct. 4 ... 5 ... 8 °C If the collector temperature falls below the value set here, the solar pump is on.
Collector cooling function Yes Collector array 1 is actively cooled via the connected emergency cooler when 100 °C is exceeded
(= Max. collector temp. – 20 °C).
No
Collector cooling function switched off.
Menu item Adjustment range Function description
Table 17
WARNING: Risk of scalding!
If DHW temperatures above 60 °C are set or thermal
disinfection is switched on, a mixing valve must be
installed.
Menu item Adjustment range Function description
Max. temp. cyl. 1 Off 1st cylinder is not heated.
20 ... 60 ... 90 °C
If the temperature set here is exceeded in cylinder 1, the solar pump is off.
Max. temp. cyl. 2 Off 2nd cylinder is not heated.
20 ... 60 ... 90 °C
If the temperature set here is exceeded in cylinder 2, the solar pump is off or the valve is closed (depending on which
function is selected).
Max. pool temp. Off The swimming pool is not heated.
20 ... 25 ... 90 °C
If the temperature set here is exceeded, the solar pump is off or the valve is closed (depending on which function is
selected).
Max. temp. cyl. 3 Off 3rd cylinder is not heated.
20 ... 60 ... 90 °C
If the temperature set here is exceeded in cylinder 3, the solar pump is off, the pump is off or the valve is closed
(depending on which function is selected).
Priority cylinder Cylinder 1 The cylinder set here is the high priority cylinder; function Cylinder 2 with valve (B), Cylinder 2 with pump (C) and
Cylinder 3 with valve (N). The cylinders are heated in the following order:
Priority cylinder 1: 1 – 2 or 1 – 2 – 3
Priority cylinder 2: 2 – 1 or 2 – 1 – 3
Priority cylinder 3: 3 – 1 2
Cylinder 2
(swimming pool)
Cylinder 3
(swimming pool)
Test interval priority cyl. 15 ... 30
... 120 min
If the low priority cylinder is currently being heated, the solar pumps are switched off at the regular intervals specified
here.
Test duration priority cyl. 5 ... 10 ... 30 min While the solar pumps are switched off ( Test interval priority cyl.), the temperature in the collector increases and
the required temperature differential for heating the high priority cylinder may be reached during this period.
Runtime valve cyl. 2 10 ... 120 ... 600 s The elapsed time set here determines how long it takes the 3-way valve to switch from cylinder 1 to cylinder 2, or vice
versa.
Start diff. heat ex. 6 ... 20 K If the differential set here between the cylinder temperature and the temperature at the heat exchanger is exceeded
and all conditions for switching on have been met, the cylinder primary pump is on.
Stop diff. heat ex. 3 ... 17 K If the differential between the cylinder temperature and the temperature at the heat exchanger falls below the value
set here, the cylinder primary pump is off.
Frost prot. temp. heat ex. 3 ... 5 ... 20 °C If the temperature at the external heat exchanger falls below the temperature set here, the cylinder primary pump is
on. This protects the heat exchanger from damage from freezing.
Table 18
33


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch MS 200 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch MS 200 in the language / languages: English, German, Dutch, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 18,85 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info