6 720 815 257 (2014/10)MS 200
CH backup mixed (H) ()
Mixed solar central heating backup with buffer or combi cylinder ( Fig. 21, page 174)
Only available if Central heating backup (A) or Central heating backup cyl 2 (D) is selected.
Function same as Central heating backup (A) or Central heating backup cyl 2 (D); in addition, the return
temperature is regulated to the specified flow temperature via the mixer.
Transfer system (I)
Transfer system with solar-heated pre-heating cylinder for DHW heating ( Fig. 29, page 179)
If the temperature of the preheating cylinder (cylinder 1 – left) exceeds the temperature of the standby
cylinder (cylinder 3 – right) by the set switch-on temperature differential, the transfer pump is switched on.
Transfer system with HE (J)
Transfer system with buffer cylinder ( Fig. 30, page 180)
DHW cylinder with internal heat exchanger.
If the temperature of the buffer cylinder (cylinder 1 – left) exceeds the temperature of the DHW cylinder
(cylinder 3 – right) by the set switch-on temperature differential, the transfer pump is switched on.
Therm.dis./daily heat-up (K)
Thermal disinfection to prevent legionella ( HSE ACOP L8 for UK) and daily heating up of the DHW cylinder/s
The entire volume of hot water is heated up on a weekly basis for half an hour to at least the temperature that
has been set for thermal disinfection.
The entire volume of hot water is heated up on a daily basis to the temperature that has been set for daily
heat-up. This function is not executed if the domestic hot water has already reached the temperature within
the last 12 hours as a result of solar heating.
In the solar system configuration, the illustration does not show that this function was added. “K” is added to the
designation of the solar system.
Heat meter (L)
Selecting the heat meter enables the yield calculation to be activated.
Based on the measured temperatures and the flow rate, the heat usage is calculated taking account of the
glycol content in the solar circuit.
In the solar system configuration, the illustration does not show that this function was added. “L” is added to the
designation of the solar system.
Notice: The yield calculation only provides correct values if the heat meter operates at 1 pulse/litre.
Temp differential controller (M)
Freely-configurable temperature differential controller (only available when the MS 200 is combined with the
MS 100, Fig. 32, page 181)
A pump or a valve is controlled via the output signal depending on the temperature differential between the
temperature at the heat source and at the heat sink and the switch-on/switch-off temperature differential.
Cylinder 3 with valve (N)
3nd cylinder with priority/secondary control via 3-way valve ( Fig. 34, page 183)
Selectable priority cylinder (cylinder 1 – top left, cylinder 2 – bottom left, cylinder 3 – top right)
Cylinder charging only switches over to the low priority cylinder via the 3-way valve if the high priority
cylinder cannot be heated any further.
While the low priority cylinder is being heated, the solar pump is switched off at adjustable test intervals for
the duration of the test in order to check whether the high priority cylinder can be heated up (change-over
check).
Table 3
6 720 647 922-25.1O
6 720 647 922-26.1O
6 720 647 922-27.1O
6 720 647 922-28.1O
V
6 720 647 922-35.1O
6 720 647 922-29.1O
6 720 807 456-03.1O
23


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch MS 200 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch MS 200 in the language / languages: English, German, Dutch, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 18,85 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info