Troubleshooting
39
Condens 7000 WP – 6721841195 (2022/01)
11 Troubleshooting
11.1 Operating and fault displays
11.1.1 General information
Fault code: indicates which fault is present.
Fault category: indicates what kind of fault is present and its effects.
Fault category O (operating code)
Operating codes indicate the operating conditions in normal operation.
Fault category B (blocking faults)
Blocking faults result in the heating system being shut down temporarily.
The heating system restarts automatically as soon as the blocking fault is
removed.
Fault category V (locking faults)
Locking faults result in the heating system being shut down, and the
system can only be restarted after a reset.
Press the and keys, until Reset is displayed.
The appliance resumes operation.
If a fault persists:
Rectify the fault according to 10.1.2 Fault code table
Fault category W (service displays)
Service displays indicate that a maintenance or repair has to be carried
out. The device is still in operation. If the service display has been caused
by a defect, under certain circumstances, it may continue running with
restricted functions.
11.1.2 Fault code table
Fault
code
Fault
category
Fault text on the display, description Remedy
200 O Boiler in heating mode
201 OBoiler in hot water mode
202 O Boiler in anti-cycle mode
203 OBoiler in standby, no heat energy demand
204 O Current prim. water temp. higher than set
val.
208 OChimney sweep demand
214 V Fan shut down during safety time 1. Check the plug on the fan.
2. Check the connecting lead to the fan.
224 VMaximal flue gas thermostat or heat
exchanger maximal thermostat has
activated
Heating circuit:
1. Check that the heating water is circulating correctly.
2. Open the closed valve in the heating circuit.
3. Top up water until the preset pressure is reached.
4. Connect the plug to the heating block temperature limiter correctly.
5. Check heating block temperature limiter, replace if required.
Potable water circuit:
Check that the potable water in the cylinder circuit is circulating correctly.
227 V No flame signal after ignition 1. Open the main shut-off valve.
2. Open the device shut-off valve.
3. Interrupt the power supply of the appliance and check the gas line.
4. Check the supply pressure of the gas line.
5. Check that the burner is working correctly, adjust burner if necessary.
6. Check CO2 content of combustion air, adjust if necessary.
7. Establish protective conductor connection (PE) in the control device.
8. Carry out function check for ignition.
9. Carry out function check for ionisation.
10.Connect the plug for the ionisation and ignition sections correctly.
11.Connect the plug for the air/gas ratio control valve correctly.
12.Check condensate pipes.
13. Check flue gas side of heat exchanger for pollution.
14.Check flame sense electrode, replace if necessary.
15.Check ignition electrode, replace if necessary.
16.Check ignition electrode connecting lead, replace if necessary.
17.Check flame sense electrode connecting lead, replace if necessary.
18.Check air/gas ratio control valve, replace if necessary.
19.Check control device/burner control unit, replace if necessary.
228 VFlame signal without flame present 1. Check ionisation cable, replace if necessary.
2. Check electrode set, replace if necessary.
3. Replace the control device.
39


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Condens GC7000WP at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Condens GC7000WP in the language / languages: English as an attachment in your email.

The manual is 15.02 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Bosch Condens GC7000WP

Bosch Condens GC7000WP User Manual - English - 12 pages

Bosch Condens GC7000WP Installation Guide - German - 60 pages

Bosch Condens GC7000WP User Manual - German - 12 pages

Bosch Condens GC7000WP Installation Guide - Dutch - 56 pages

Bosch Condens GC7000WP User Manual - Dutch - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info