Troubleshooting
41
Condens 7000 WP – 6721841195 (2022/01)
349 BDifference between flow and return
temperature too high
1. Open the shut-off valves.
2. If the water pressure is too low, top up with water and vent the system.
3. Open a thermostat valve.
4. Replace flow or return sensor if required.
5. Replace the pump if required.
357 O Ventilation program
358 OAnti-seizing functn. active
360 V System fault boiler electronics / basic
controller
1. Install boiler identification module/coding plug.
2. Connect plug to boiler identification module/coding plug.
3. Replace boiler identification module/coding plug (Bosch contact customer service).
362 VBoiler identification module or boiler
electronics faulty
Replace boiler identification module/coding plug (Bosch contact customer service).
363 V System fault boiler electronics / basic
controller
Replace control device/burner control unit.
811 AHot water heating: thermal disinfection
failed
1. If water is being drawn constantly, take action to stop this.
2. Position the DHW temperature sensor correctly.
3. Check that there is contact between the DHW cylinder temperature sensor and the
cylinder.
4. Vent the cylinder circuit.
5. Set DHW heating to "priority".
6. Check plate heat exchanger for calcification.
7. Check sizing of DHW circulation line and heat loss.
815 W Low loss header temp. sensor faulty 1. Check hydraulic configuration, correct if necessary.
2. Check sensor for breaks or short circuits, replace if necessary.
1010 O No communication via EMS BUS connection 1. Rectify wiring fault and switch the control unit off and on again.
2. Repair the BUS cable or replace it.
3. Replace faulty EMS-BUS node.
1013 W Max. combustion point reached 1. Carry out maintenance.
2. Reset service display.
1017 W System pressure too low 1. Top up water and vent the system.
2. Check the pressure sensor, replace if necessary.
1018 W Maintenance interval expired 1. Carry out maintenance.
2. Reset service display.
1019 W Incorrect pump type detected 1. Check pump cabling.
2. Check that the correct heating pump type is in the appliance, replace if necessary.
1022 W Cylinder temp. sensor faulty or contact
problems
1. Connect the plug to the temperature sensor correctly.
2. Connect the plug to the control device correctly.
3. Check the temperature sensor, replace if necessary.
4. Check temperature sensor connecting lead, replace if necessary.
1023 Maximum run time including standby time
reached
1. Carry out maintenance.
2. Reset service display.
1025 W Return temp. sensor is faulty 1. Connect the plug to the return temperature sensor correctly.
2. Replace return temperature sensor.
3. Replace connecting lead to return temperature sensor.
4. Replace control device.
1037 W Outside temp. sensor faulty - heating back-
up operation active
1. If an outside temperature sensor is not desired. Select the room temperature-
dependent configuration in the control device.
2. If there is no continuity, rectify the fault.
3. Clean corroded terminals in the outside sensor housing.
4. If values do not match, replace the sensor.
5. If the sensor values matched, but the voltage values do not match, replace the control
unit.
1065 W System pressure sensor faulty or not
connected
1. Connect the plug to the pressure sensor correctly.
2. Check pressure sensor connecting lead, replace if necessary.
3. Check the pressure sensor, replace if necessary.
Fault
code
Fault
category
Fault text on the display, description Remedy
41


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Condens GC7000WP at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Condens GC7000WP in the language / languages: English as an attachment in your email.

The manual is 15.02 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Bosch Condens GC7000WP

Bosch Condens GC7000WP User Manual - English - 12 pages

Bosch Condens GC7000WP Installation Guide - German - 60 pages

Bosch Condens GC7000WP User Manual - German - 12 pages

Bosch Condens GC7000WP Installation Guide - Dutch - 56 pages

Bosch Condens GC7000WP User Manual - Dutch - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info