Operation
Condens 7000 WP – 6721841195 (2022/01)
30
Max. output 10 ... 100 % Pump output at maximum heat output. Only available if
Pump range map is set to 0.
Pump block time 0 ... 24 × 10 seconds The internal pump is locked until the external 3-way valve
has reached its end position.
Pump overrun 1 2 ... 60 min, 24 h Overrun time of the heating pump: pump overrun begins
when heat demand ends.
Ventilation func. Off
•Auto
•On
The venting function can be switched on after
maintenance work.
During ventilation, the following appears in the info area
of the standard display Ventilation func.
Siphon fill. prog. Off (only permitted when maintenance is in
progress)
On, boiler min.
On, heating min.
The siphon filling program is activated in the following
cases:
Once the device is switched on using the On/Off
switch
Once the burner was not in operation for at least
28 days
Once the operating mode is switched from summer to
winter mode
Once the factory settings of the device have been
restored
The next time there is a heat demand for heating, the
appliance is held at low heat output for 15 minutes. The
siphon filling program remains active until the device was
in operation with low heat output for 15 minutes.
When the trap filling program is running, the following
appears in the info area of the standard display Siphon
fill. prog.
3-WV mid. pos. No
•Yes
The function ensures that the system is fully drained and
that the motor can be easily removed. The 3-way valve
remains at the middle position for approx. 15 minutes.
Min. Sys. Pres. 0.6 0.8 bar
Target Sys. Pres. 1.0 … 1.3 … 1.7 bar
Maintenance
Maintenance type Without
Burner run time: 1000 ... 6000 h
Service date1)
Boiler run time: 1 ... 72 months
Limit values
Max. flow temp. 30 ... 85 °C Limits the adjustment range for the flow temperature.
Max. DHW temp. 35 ... 60 ... 80 °C Limits the adjustment range for the domestic hot water
temperature.
Min. boiler outp. 14 ... 50% Minimum heat output. Minimum setting value may vary
depending on appliance output.
Heating curve
Enable Yes
No
When connecting a weather-compensated control unit,
no adjustment at the device is required. The system
control unit optimises this setting. This service function
activates a simple, weather-compensated controller with
a linear heating curve. Depending on the on/off input, the
heating is switched on or off.
Htg. curve base 20 … 90 °C This is only displayed if the control unit was activated.
This can be used to set the base point of the heating
curve, which corresponds to an outside temperature of
+20 °C.
Htg. curve end 20 ... 90 °C This is only displayed if the control unit was activated.
This can be used to set the base point of the heating
curve, which corresponds to an outside temperature of -
10 °C.
Meu item Settings/adjustment range Remark/restriction
30


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Condens GC7000WP at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Condens GC7000WP in the language / languages: English as an attachment in your email.

The manual is 15.02 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Bosch Condens GC7000WP

Bosch Condens GC7000WP User Manual - English - 12 pages

Bosch Condens GC7000WP Installation Guide - German - 60 pages

Bosch Condens GC7000WP User Manual - German - 12 pages

Bosch Condens GC7000WP Installation Guide - Dutch - 56 pages

Bosch Condens GC7000WP User Manual - Dutch - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info