Installation instructions
11
Fig. 6
A 27” minimum vertical clearance is required to remove
the filter for cleaning and to replace the anode rod. The
hot and cold water plumbing and electrical connections
must not interfere with the removal of the filter.
Fig. 7
Condensation drain
The unit has a condensate drain, therefore a drain must
be available in close proximity to the unit. The drain must
be no higher than 36” above the floor (laundry drain is
acceptable).
If no drain is available, then a common condensate
pump with a capacity no less than 1 gallon/day must be
purchased from a local builder and supply store and
installed.
3.3 Venting (specifications and vent
runs)
Venting the outlet air of the water heater to another
room may be an option for specific applications. See
Section 3.6.
Duct diameter: 8”
Maximum outlet duct length: 16.5 feet
Maximum Air flow: 219 CFM
Maximum no. of elbows: 1.
The vent collar accessory (see Fig. 2) must be installed
in order to accommodate the required 8" diameter vent
pipe. Line up tabs on vent collar with slots in vent
opening. Rotate to lock into place.
If terminating venting to the outdoors, pitch horizontal
pipe downward towards termination 1/4" per foot to
avoid damage from rain.
3.4 Water piping
3.4.1 Inlet - Outlet connections
Refer to the illustration below for suggested typical
installation. The installation of unions or flexible copper
connectors is recommended on the hot and cold water
connections so that the water heater may be easily dis-
connected for servicing if necessary. The HOT and
COLD water connections are clearly marked and are
¾”NPT on all models.
IMPORTANT: Do not apply heat to the HOT or COLD
water connections. If sweat connections are used,
sweat tubing to adapter before fitting the adapter to the
water connections on heater. Any heat applied to the
hot or cold water connection will permanently damage
the dip tube.
Fig. 8 Typical installation
3.4.2 Dielectric union (recommended acces-
sory)
Different metals between plumbing and tank materials
and additionally the effect of hot water can cause
corrosion of one of the metals (generally the one in the
tank is the metal attacked)
The Dielectric union will avoid any physical contact
between the two metals, acting as an effective insulator
and preventing this attack. How quick this corrosion
progresses, if at all, depends on the content of your
water, its pH, the dissolved minerals and the metals
involved.
27”
6720646804-05.1V
i
Install a shut-off valve in the cold water line
near the water heater. This will enable eas-
ier service or maintenance of the unit later.
6720646804-09.1V
6” air gap
Relief discharge
line to suitable
open drain
6’ drain hose
Thermal expansion
tank (if required)
To cold water
supply
Hot water outlet
to fixtures
Union
Union
Temperature and
pressure relief valve
(shown in different
location for clarity)
Drain valve
Jacket
access panel
Jacket
access panel
Auxiliary catch
pan 2” maximum
Electrical junction box
(use only copper
conductors)
To electrical
distribution panel
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Compress 3000 - HP 200-1 E AI-F at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Compress 3000 - HP 200-1 E AI-F in the language / languages: English as an attachment in your email.

The manual is 1,37 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info