Installation instructions
13
of the relief valve, and possibly the heater itself.
Replacing the relief valve will not correct the problem!
The suggested method of controlling thermal expansion
is to install an expansion tank in the cold water line
between the water heater and the check valve. The
expansion tank is designed with an air cushion built in
that compresses as the system pressure increases,
thereby relieving the over-pressure condition and
eliminating the repeated operation of the relief valve.
Other methods of controlling thermal expansion are
also available. Contact your installing contractor, water
supplier or plumbing inspector for additional information
regarding this subject.
3.5 Electric requirements
Power requirements
Check the markings on the rating plate of the water
heater to be certain the power supply corresponds to
the water heater requirements.
Electrical connections
A separate branch circuit with copper conductors, over-
current protective device and suitable disconnecting
means must be provided by a qualified electrician.
All wiring must conform to local codes or latest edition
of National Electrical Code ANSI/NFPA 70.
The water heater is completely wired to the junction box
at the top of the water heater. An opening for ½” or ¾”
electrical fitting is provided for field wiring connections.
The voltage requirements and wattage load for the
water heater are specified on the rating label on the
front of the water heater.
The branch circuit wiring should include either:
Metallic conduit or metallic sheathed cable approved
for use as a grounding conductor and installed with
fittings approved for the purpose.
Non metallic sheathed cable, metallic conduit or
metallic sheathed cable not approved for use as a
ground conductor shall include a separate conductor
for grounding. It should be attached to the ground
terminals of the water heater and the electrical distri-
bution box.
Fig. 10 Water heater junction box
This water heater must be connected to the building
electrical system on a dedicated branch circuit. A
25amp circuit breaker must be installed for overcurrent
protection.
This water heater must be connected to the building's
electrical supply with 10AWG copper wire or larger.
If higher wattage elements are installed, consult the
National Electrical Code (NFPA 70) to determine the
proper circuit breaker and minimum wire size.
Caution: Do not mis-wire electrical
connections. 240V AC must be applied
to L1 and L2 wires as shown in Fig. 10.
Failure to do so will VOID the warranty.
Connecting the water heater to 120V
AC may damage the compressor or
other electrical components.
Warning: Proper ground connection
is essential. The presence of water in
the piping and water heater does not
provide sufficient conduction for a
ground. Use of non-metallic piping,
dielectric unions, flexible connectors,
etc., can cause the water heater to be
electrically isolated, which may cause
fire or shock.
13


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Compress 3000 - HP 200-1 E AI-F at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Compress 3000 - HP 200-1 E AI-F in the language / languages: English as an attachment in your email.

The manual is 1,37 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info